Chapter 8
List of Data Settings
8-2
2
1
ON
OFF
Code
Function name
Monitored data or setting
Default
Change during
RUN operation
Page
FF
FEF
FUF b031
≠
10 b031=10
d022 Life-check monitoring
1:Capacitor on main circuit board
2:Cooling-fan speed drop
4-4
d023 Program counter
0 to 1024
4-5
d024 Program number monitoring
0000 to 9999
4-5
d025 User monitor 0
-2147483647 to 2147483647 (upper 4 digits including “-“)
4-5
d026 User monitor 1
d027 User monitor 2
d028 Pulse counter
0 to 2147483647 (upper 4 digits)
4-5
d029 Position setting monitor
-1073741823 to 1073741823 (upper 4 digits including “-“)
4-5
d030 Position feedback monitor
4-5
d031 Clock monitor
* In case you use WOP (option), this monitor is activated.
d060 Inverter mode monitor
I-C(CT)/ I-v(VT)
4-5
d080 Trip Counter
0. to 9999., 1000 to 6553 (10000 to 65530) (times)
4-5
d081 Trip monitoring 1
Factor,
frequency (Hz),
current (A),
voltage across P-N (V),
running time (hours),
power-on time (hours)
4-6
d082 Trip monitoring 2
d083 Trip monitoring 3
d084 Trip monitoring 4
d085 Trip monitoring 5
d086 Trip monitoring 6
d090 Programming error monitoring Warning code
4-6
d102 DC voltage monitoring
0.0 to 999.9 (V)
4-6
d103 BRD load factor monitoring
0.0 to 100.0 (%)
4-6
d104
Electronic thermal overload
monitoring
4-6
(Note) CT : Constant torque mode, VT : Variable torque mode, you can set CT or VT by b049.
8.3 Function Mode
Code
Function name
Monitored data or setting
Default
Memo
Change during
RUN operation
Page
FF FEF FUF
b031
≠
10 b031=10
F001 Output frequency setting
0.0, "start frequency" to "maximum frequency" (or maximum
frequency, 2nd/3rd motors) (Hz)
0.0 to 100.0 (when PID function is enabled)
0.00
Allowed Allowed
4-7
F002 Acceleration (1) time setting
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
30.00
Allowed Allowed 4-10
F202
Acceleration (1) time setting,
2nd motor
30.00
Allowed Allowed 4-10
F302
Acceleration (1) time setting,
3rd motor
30.00
Allowed Allowed 4-10
F003 Deceleration (1) time setting
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
30.00
Allowed Allowed 4-10
F203
Deceleration time setting,
2nd motor
30.00
Allowed Allowed 4-10
F303
Deceleration time setting,
3rd motor
30.00
Allowed Allowed 4-10
F004 Keypad Run key routing
00 (forward rotation), 01 (reverse rotation)
00
Not
Not
4-7
Содержание SJ700D-004L
Страница 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Страница 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Страница 70: ...Chapter 3 Operation 3 25 Memo ...
Страница 248: ...Chapter 5 Error Codes 5 11 Memo ...
Страница 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...
Страница 282: ...Chapter 8 List of Data Settings 8 17 Memo ...