CHAPTER 7 COUNTERMEASURE FOR ABNORMALITY
21
7.1 Trip display
When the inverter is in a tripped state, the inverter displays an error code (See table below). The trip history
monitor (d081 to d086) also displays the same error code as the inverter.
7.2 Protection function list
The table below describes an error code for protecting the inverter and the motor.
Error Display in the table below, X is 6 (Error for option slot 1) or 7 (Error for option slot 2).
No.
Function
Error
Display
Action
1
Lonworks
communication error
EX0
This error is displayed, when disconnection occured, while
the inverter is operating with Lonworks.
2
Inverter communication
error
EX9
This error is displayed, when communication timeout occurs
between the inverter and the option board.
With regard to the other errors except table above, refer to Inverter instruction manual chapter 4 Explanation
of function.
7.3 Countermeasure for a trip state
The table below only corresponds to additional trip codes, with regard to the other countermeasures refer to
Inverter instruction manual chapter 4 Explanation of function.
Trip code
Name of trip
Cause
Conformation
Countermeasure
Defective connector
for signal cable
causes connection
fail.
Check the area of
Connection.
Improve the connection and then
reset the power supply.
Terminating resistor
is not connected.
Check the
Connection
Connect the terminating Resistor
and then reset the power supply
EX0
Lonworks
Communication
error
Wiring distance does
not much with
baudrate.
Check the wiring
Distance
Adjust the setting to the matching
Baudrate
Adjust wiring distance
EX9
Inverter
communication
error
Option board is
removed.
Check as
Mentioned left
Mount the option board again
and then secure it with screws.
Trip code
Inverter’s running condition of trip detected