![Hitachi RUA-NP20ATS Скачать руководство пользователя страница 13](http://html.mh-extra.com/html/hitachi/rua-np20ats/rua-np20ats_instruction-manual_2139427013.webp)
Table 3. Safety and Control Device Setting
Model
RUA-NP20ATS
RUA-NP30ATS
For Compressor
E505DH/E855DH
E855DH
High Pressure Switch
Automatic Reset, Non-Adjustable
Cut-Out
MPa
4.15
4.15
kg/cm
2
G
42.3
42.3
Cut-In
MPa
3.2
3.2
kg/cm
2
G
32.6
32.6
Overcurrent Relay
Automatic Reset, Non-Adjustable
230V, 60Hz
380V, 60Hz
A
A
40
---
41
21
Discharge Gas Thermostat
Cut-Out
°C
120
120
Cut-In
°C
98
98
CCP Timer for Compressor
Non-Adjustable
(built-in PCB)
No. 1
min
3
3
No. 2
min
3.5
3.5
No. 3
min
4
4
For Evaporator Fan Motor
230V, 60Hz
380V, 60Hz
A
A
14
---
21
11
For Condenser Fan Motor
Automatic Reset, Non-Adjustable
Internal Thermostat
Cut-Out
°C
160
160
Cut-In
°C
125
125
For Control Circuit Fuse
Capacity
A
5
5
6.5 Safety and Control Device Setting
9
TEST RUNNING