TEST RUNNING 

6. TEST RUNNING 

6.1 Final Installation Check 

Inspect  the  installation  work  according  to  all  documents  and  drawings.  Table  2  shows  the  minimum 
checkpoints. 

Table 2. Installation Check List 

INSTALLATION    WORK    CHECK    LIST 

1.Is the unit solidly mounted and leveled? 

 

 

2.Is the installation location adequate? 

 

 

 

  Space for Condenser Air Flow 

 

  Space for Maintenance Work 

 

  Noise and Vibration 

 

  Sunshine and Rainfall 

 

  Appearance 

3.Is the ducting work adequate? 

 

 

 

  Filter 

 

  Soundproofing 

 

  Size and Length 

 

  Insulation 

4.Are the condensate drain lines properly arranged? 

 

 

 

  Trap 

 

  Drain Ditch 

5.Is the electrical wiring system adequate? 

 

 

 

  Wire Size 

 

  Tightened Connections 

 

  Switch Size 

 

  Operation Control Devices 

 

  Fuse Size 

 

  Safety Devices 

 

  Voltage 

 

  Hz 

6. Have the shipping washers been removed from the rubber-mounted compressor? 

 

 

 

6.2 Preparation 

Tools  and  Instruments 

 

High  and  Low 

Pressure Compound Gauge(s), An Electric Tester, 
and General Tools. 

Preparation 

 

Confirm that the system switch on 

the room thermostat is at the OFF position. 

Pressure Gauges 

 

Equip high and low pressure 

compound gauges according to Fig. 11. 

Thermostat 

 

Set  the  thermostat  at  a  lower 

temperature than the room temperature. 

 

 

6.3 Test Running 

Test  running  should  be  performed  as  follows, 
when  the  unit  is  wired  according  to  the  HITACHI 
standard wiring label. 

1.  Set  the  operation  switch  to  the 

FAN 

position 

and the system switch to the 

ON

 position, and 

the  evaporator  fan  will  start  immediately. 
Check the rotation direction, fan speed and air 
flow quantity through the evaporator. 

2. Set the operation switch to the COOL position, 

and  the  compressor  and  condenser  fans  will 
start 3 minutes after this operation (refer to Fig. 
9). 

3. After system operation has become stabilized, 

check the suction and discharge pressures on 
the compound gauges 

4.  Check  the  operating  voltage,  phase  balance 

and operating current. 

5. Check to ensure that the thermostat functions 

properly. 

6.  Check  to  ensure  that  the  control  and 

protective  devices  function  properly  (refer  to 
Table 3). 

Содержание RUA-NP20ATS

Страница 1: ...NSTRUCTION MANUAL BEFORE USING THIS AIR CONDITIONER KEEP THIS MANUAL FOR FUTURE REFERENCE INSTRUCTIONS MANUAL Installation Operation and Maintenance 65MP3208 REFRIGERANT R410A Models AIR CONDITIONERS RUA NP30ATS RUA NP20ATS SELF CONTAINED ...

Страница 2: ...he following temperatures Operate the air conditioner within this range Condenser Air Inlet Temperature and Evaporator Air Inlet Temperature This manual should be considered as a permanent part of the air conditioning equipment and should remain with the air conditioning equipment Hitachi s air conditioners are designed and manufactured based on using the specified refrigerants The applicable refr...

Страница 3: ...LECTRICAL WIRING 3 3 1 Main Power Wiring Procedures 3 4 FAN SPEED ADJUSTMENT 6 5 REMOVING SHIPPING WASHERS 6 6 TEST RUNNING 7 6 1 Final Installation Check 7 6 2 Preparation 7 6 5 Safety and Control Device Setting 9 7 MAINTENANCE 10 8 WINTER SHUTDOWN 11 9 REPLACEMENT OF PARTS 11 7 10 TROUBLESHOOTING 13 6 3 Test Running 6 4 Test Running Record 8 3 2 Control Wiring 4 3 3 Printed Circuit Board PCB Lay...

Страница 4: ...at the thermostat is set at the desired position 3 Check the air filter for clogging 4 Are there any obstacles which hamper free air Please contact your service shop if the trouble is still not solved Maintenance 1 Clean or replace the filter 2 Clean the cabinet with cleaner 3 Clean the condensate drain pan and the drain piping 4 Clean the condenser It is recommended that a specialist be contacted...

Страница 5: ...oftop or on the ground installation Additionally for on the ground installation provide a gravel or concrete space around the condenser air intake in order to avoid airflow obstruction due to grass or other vegetation Unit Check to ensure that the unit has been transported without damage File a damage claim with the transportation companies if mishandling due to transportation company negligence i...

Страница 6: ...ituated to balance the unit refer to the center of gravity in Fig 4 Lifting by Forklift Insert the forks under the base frames from the indicated direction in Fig 4 Lift the unit exercising care to catch both of the outer frames Rigging Apply spreader bars to the top of the unit in order to prevent damage to the unit due to cable scratches Unpacking Follow the instructions marked on the packing NO...

Страница 7: ...upplied main switch box at the properly selected location 2 Install conduit connectors in the hole for power wiring knockout holes 3 Lead the main power wires and the earthing wire through the connector to the screw terminals for main power and earthing in the magnetic switch box The neutral wire to 220V power supplies should also be led through the connector Firmly connect the wires with wire ter...

Страница 8: ...recommended when the unit is started after installation of the unit 1 If the phase is wrong exchange two of the three wires connected from the main power source to the main terminals of the unit as indicated with dotted lines and then check the rotation direction of the phase sequence indicator once again Do not exchange the wires in the unit in order to protect the compressor against the reversal...

Страница 9: ...t Refer to 3 2 Control Wiring 3 Times Trip Detected of Safety Device 1 Check the current for indoor fan motor 2 Check the current for outdoor fan motor 3 Check the pressure of discharge and suction line Refer to 16 Troubleshooting 4 Check the internal thermostat of compressor 4 Times Overcurrent of Compressor 1 Check the current for compressor motor 2 Check the pressure of discharge and suction li...

Страница 10: ...ghtening the bolts on the adjusting bracket 3 Turn the movable pulley flange toward the fixed flange to increase the speed and turn it away from the fixed flange to decrease the speed Each turn of the movable flange will increase or decrease the fan speed by 32 rpm Fig 7 Adjustable Motor Pulley Table 1 Fan Speed Adjustment RPM Fan Speed RPM PD Pitch Diameter of Motor Pulley mm RPM Turn Fan Speed C...

Страница 11: ...and General Tools Preparation Confirm that the system switch on the room thermostat is at the OFF position Pressure Gauges Equip high and low pressure compound gauges according to Fig 11 Thermostat Set the thermostat at a lower temperature than the room temperature 6 3 Test Running Test running should be performed as follows when the unit is wired according to the HITACHI standard wiring label 1 S...

Страница 12: ...N ON ON ON OFF ON 2nd ON ON ON OFF OFF ON Electric Components Indoor Fan Motor MIF Outdoor Fan Motor 1 2 MOF1 2 After 3 min and After 3 min 30 sec After 4 min 4 Start Delay Time Safety Devices Close Close Close Close Close Close Close Close Open After 3 min and After 3 min 30 sec After 4 min 4 Compressor 1 2 MC1 2 Compressor 3 4 MC3 4 Start Delay Time RUA NP30ATS RUA NP20ATS Compressor 3 MC3 Compr...

Страница 13: ...Reset Non Adjustable 230V 60Hz 380V 60Hz A A 40 41 21 Discharge Gas Thermostat Cut Out C 120 120 Cut In C 98 98 CCP Timer for Compressor Non Adjustable built in PCB No 1 min 3 3 No 2 min 3 5 3 5 No 3 min 4 4 For Evaporator Fan Motor 230V 60Hz 380V 60Hz A A 14 21 11 For Condenser Fan Motor Automatic Reset Non Adjustable Internal Thermostat Cut Out C 160 160 Cut In C 125 125 For Control Circuit Fuse...

Страница 14: ...porator Fan Check for a loosened fan belt and abnormal sounds Lubrication Compressor The compressors are charged at the factory with the correct oil and the compressor nameplate It is not necessary to add oil if the cycle remains sealed Refrigerant Cycle Strainer Check for clogging after the time when the cycle is opened Refrigerant Re Charge When the cycle requires re charging due to leakage or r...

Страница 15: ... and dry the unit especially the drain pan and the drain lines This unit shall be preferably covered during shutdown in order to protect it from dust and environmental conditions Spring Start Up After any extended shutdown period prepare the unit for operation as follows 1 Thoroughly inspect and clean the unit 2 Clean or replace the air filters 3 Clean the condensate drain lines 4 Remove any accum...

Страница 16: ...ction line Temperature and superheat Suction line Temperature C Superheat C 8 Check Pressures Discharge Pressure kg cm2G Suction Pressure kg cm2G 9 Check Voltage Rated Voltage V Operation Voltage R S V S T V T R V Starting Voltage V Phase Imbalance 1 V Vm 10 Check Compressor input and running current Input kW Running Current A 11 Do the control devices function properly 12 Do the protective device...

Страница 17: ...ce the Contactor Repair the Contacts Replace the Compressor Correct the Wiring No Voltage or Low Voltage Single Phase Shorted Components Loose Connections High Voltage or Low Voltage Single Phase or Phase Imbalance Faulty Fan Bearing Excessive Fan Belt Tension Excessive Fan Load Burned Coil Faulty Contact Defective Operation Switch High Voltage or Low Voltage Single Phase or Phase Imbalance Burned...

Страница 18: ...ction Pressure Low Discharge Pressure Add Refrigerant See Unit Working Range Operating High Discharge Pressure or Low Suction Pressure Clogged Capillary of Pressure Switch High or Low Pressure Switch Tripped Overcurrent Relay for Compressor Compressor Cycling Insufficient Cooling High Discharge Pressure and High Suction Pressure Loose Connections High Suction Pressure High Discharge Pressure or Lo...

Страница 19: ...ed Screws See the Installation Guide Clean the Flexible Ducts Evaporator Air Inlet Temperature High Suction Pressure High Excessive Fresh Air Intake Insufficient Duct Insulation Defective Compressor Valve Overcharged Refrigerant High Discharge Pressure Evaporator Air Flow Low Suction Pressure Restricted Clogged Air Filter Slipping Fan Belt Restricted Duct Low Fan Speed Faulty Fan Motor Short Cycli...

Страница 20: ...65MP3208 Printed in the Philippines ...

Отзывы: