background image

 

 

INSTALLATION 

Model 

Dimensions (mm) 

Weight 

(kg) 

RUA-NP13ATS 

900 

700 

1,180 

785 

580 

RUA-NP15ATS 

900 

700 

1,180 

785 

610 

RUA-NP20ATS 

1,000 

900 

1,325 

1,125 

790 

RUA-NP25ATS 

1,000 

900 

1,650 

1,350 

900 

RUA-NP30ATS 

1,150 

850 

1,650 

1,350 

1,055 

 

Fig. 4. Center of Gravity 

 

2. INSTALLATION

2.1 Ducting Arrangement 

Tools  and  Instruments 

  General  tools  for 

ducting. 

Connection 

  Pre-drilled  duct  flanges  are 

provided  at  the  supply  and  return  air  duct 
connections.  A  field-supplied  or  optional  filter  box 
with filter must be installed at a proper location in 
the return air duct. It is recommended that flexible 
duct  connections  be  installed  to  minimize  sound 
and  vibration  transmission.  All  ducts  running 
outside  must  be  sufficiently  insulated  and 
weatherproofed. 

2.2 Condensate Drain Piping 

Tools and Instruments 

 General piping tools. 

Drain  Trap 

  A  female  piping  thread  screw 

connection  is  provided  at  side  of  the  unit. 
Dimension  "L"  in  Fig.  5  should  be  sufficiently 
longer than the negative fan pressure at the drain 
connection  (50mm  to  100mm,  depending  on  the 
return  air  duct  design).  Always  fill  the  trap  with 
water. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 5. Condensate Drain Connection 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
    For Models RUA-NP13ATS through RUA-NP20ATS            For Models RUA-NP25ATS and RUA-NP30ATS 
 

Содержание RUA-NP13ATS

Страница 1: ...NUAL SELF CONTAINED AIR CONDITIONERS Models RUA NP13ATS RUA NP15ATS RUA NP20ATS RUA NP25ATS RUA NP30ATS REFRIGERANT R410A IMPORTANT READ AND UNDERSTAND THIS INSTRUCTION MANUAL BEFORE USING THIS AIR CONDITIONER KEEP THIS MANUAL FOR FUTURE REFERENCE 65MP3179 ...

Страница 2: ...Wet Bulb Maximum Minimum Maximum Minimum All Models 52 C 125 F 20 C 68 F 35 C 21 5 C 95 F 70 5 F 19 5 C 14 C 67 F 57 F NOTES 1 When the unit is operating at a condenser air inlet temperature of 52 C DB 125 F DB the maximum evaporator air inlet temperature shall be 18 C WB 64 4 F WB 2 RUA NP4ATS RUA NP5ATS RUA NP9ATS and RUA NP10ATS 80 to 120 of Nominal Air Flow RUA NP6ATS and RUA NP8ATS 80 to 115 ...

Страница 3: ...TRICAL WIRING 4 3 1 Main Power Wiring Procedures 4 3 2 Control Wiring 4 3 3 Printed Circuit Board PCB Layout 5 4 FAN SPEED ADJUSTMENT 9 5 REMOVING SHIPPING WASHERS 10 6 TEST RUNNING 11 6 1 Final Installation Check 11 6 2 Preparation 11 6 3 Test Running 11 6 4 Test Running Record 12 6 5 Safety and Control Device Setting 16 7 MAINTENANCE 17 8 WINTER SHUTDOWN 18 9 REPLACEMENT OF PARTS 18 10 TROUBLESH...

Страница 4: ...Unit Does Not Start 1 Is the main power source switch to the unit ON 2 Is the main fuse normal 3 Is the phase of main power source right Poor Cooling Operation 1 Are there any obstacles which hamper sufficient air to the condenser 2 Check to ensure that the thermostat is set at the desired position 3 Check the air filter for clogging 4 Are there any obstacles which hamper free air flow to the room...

Страница 5: ...the condenser air intake in order to avoid airflow obstruction due to grass or other vegetation Unit Check to ensure that the unit has been transported without damage File a damage claim with the transportation companies if mishandling due to transportation company negligence is suspected 1 2 Transportation Secure the route to the final installation location by confirming the packing dimensions se...

Страница 6: ... unpacking is performed Keep the unit upright When transporting the unit after unpacking has been performed take note of the following Rolling Place three equal sized rollers under the base frames Each roller must carry both of the outer frames and must be situated to balance the unit refer to the center of gravity in Fig 4 Lifting by Forklift Insert the forks under the base frames from the indica...

Страница 7: ...be installed at a proper location in the return air duct It is recommended that flexible duct connections be installed to minimize sound and vibration transmission All ducts running outside must be sufficiently insulated and weatherproofed 2 2 Condensate Drain Piping Tools and Instruments General piping tools Drain Trap A female piping thread screw connection is provided at side of the unit Dimens...

Страница 8: ...ched to the magnetic switch box A scroll compressor is equipped Because that the rotation direction of the orbiting scroll of the HITACHI scroll type compressor is fixed therefore a reverse single phase sequence protection relay is equipped in this unit If each phase R S or T of the power source is incorrectly connected the compressor does not start due to the activation of the reverse single phas...

Страница 9: ... T Current Transformer for NO 1 Compressor DSW1 Dip Switch for Capacity Setting CT2 R S T Current Transformer for NO 2 Compressor DSW2 Dip Switch for Optional Function Setting 1 CT3 R S T Current Transformer for NO 3 Compressor DSW3 Dip Switch for Optional Function Setting 2 CT4 R S T Current Transformer for NO 4 Compressor DSW4 Dip Switch for Optional Function Setting 3 CN6 Connector for Transfor...

Страница 10: ...e switches are set without turning off the power source the contents of the setting are invalid Mark of indicates the position of dip switch DSW2 Optional Function Setting 1 Number of Compresser Dip Switch Setting Force No 1 Compressor Stop Force No 2 Compressor Stop Force No 3 Compressor Stop Force No 4 Compressor Stop 3 3 5 Alarm History Check 1 First to push SW1 continually for more than 3 seco...

Страница 11: ...or2 Internal thermostat for compressor2 acted Check the Internal Thermostat of Compressor2 C3 Overheat for Compressor3 Internal thermostat for compressor3 acted Check the Internal Thermostat of Compressor3 C4 Overheat for Compressor4 Internal thermostat for compressor4 acted Check the Internal Thermostat of Compressor4 19 Overcurrent for Indoor Fan Motor Check the Current for Indoor Fan Motor 31 N...

Страница 12: ... C2 Low Pressure Switch PS L 2 Acted Check the Suction Pressure for Compressor2 Refer to 10 Troubleshooting C3 Low Pressure Switch PS L 3 Acted Check the Suction Pressure for Compressor3 Refer to 10 Troubleshooting C4 Low Pressure Switch PS L 4 Acted Check the Suction Pressure for Compressor4 Refer to 10 Troubleshooting F1 57 Overheat for Outdoor Fan Motor1 Internal thermostat for outdoor fan moto...

Страница 13: ...he fan speed by 39 to 45 rpm 4 Tighten the set screw in the movable pulley which is positioned over the flat surfaces of the fixed pulley 5 Adjust the belt tension approximately 20 mm deflection with one finger by pushing the motor downward and tightening the bolts on the adjusting bracket For Model RUA NP13ATS and RUA NP15ATS Fig 7 1 Adjustable Motor Pulley Table 1 1 Fan Speed Adjustment Models X...

Страница 14: ...0 5 137 3 134 1 131 0 127 7 124 6 7 5 860 126 1 43 RPM 1020 1000 980 960 940 915 895 870 850 RUA NP30ATS PD 150 0 146 9 143 7 140 5 137 3 134 1 131 0 127 7 124 6 4 0 940 137 3 43 RPM 1020 1000 980 960 935 915 895 870 850 RPM Fan Speed rpm PD Pitch Diameter of Motor Pulley mm RPM Turn Fan Speed Change per One Turn of Movable Motor Pulley 5 REMOVING SHIPPING WASHERS These compressors are mounted on ...

Страница 15: ...t the operation switch to the COOL position and the compressor and condenser fans will start 3 minutes after this operation refer to Fig 9 3 After system operation has become stabilized check the suction and discharge pressures on the compound gauges Normal operating pressures are shown in Fig 10 4 Check the operating voltage phase balance and operating current 5 Check to ensure that the thermosta...

Страница 16: ...n Motor 1 2 MOF1 2 Outdoor Fan Motor 3 4 MOF3 4 RUA NP13ATS and RUA NP15ATS Normal Start 2 Compressor 1 MC1 Compressor 2 MC2 Reverse Start 2 Compressor 1 MC1 Compressor 2 MC2 Start Delay Time RUA NP20ATS through RUA NP30ATS Normal Start 2 Compressor 1 2 MC1 2 Compressor 3 4 MC3 4 Reverse Start 2 Compressor 1 2 MC1 2 Compressor 3 4 MC3 4 Start Delay Time Safety Devices Close Close Close Close Close...

Страница 17: ...13 TEST RUNNING For Compressor Model E856DH For Compressor Model E506DH Fig 10 1 Nominal Operation Pressures for Model RUA NP13ATS Fig 10 2 Nominal Operation Pressures for Model RUA NP15ATS ...

Страница 18: ...NP25ATS indicate the imaginary line for non fan cycling control Add the following values for obtaining the pressures under the fan cycling control kg cm2G Model Discharge Pressure Suction Pressure No 1 Cycle No 2 Cycle No 3 Cycle No 1 Cycle No 2 Cycle No 3 Cycle RUA NP20ATS 6 0 7 0 6 0 1 0 1 0 1 0 RUA NP25ATS 2 0 2 0 2 0 1 0 1 0 1 0 Fig 10 4 Nominal Operation Pressures for Model RUA NP25ATS ...

Страница 19: ...15 TEST RUNNING Fig 10 5 Nominal Operation Pressures for Model RUA NP30ATS ...

Страница 20: ... 1 0 70 7 1 0 40 4 1 0 70 7 1 Overcurrent Transformer Automatic Reset Non Adjustable Cut Out A 18 0 10 6 18 0 18 0 10 6 18 0 18 0 Internal Thermostat Automatic Reset Non Adjustable Cut Out Cut In C C 130 108 130 108 130 108 130 108 130 108 CCP Timer for Compressor Building on PCB Non Adjustable No 1 No 2 No 3 No 4 min min min min 3 3 5 3 3 5 3 3 5 4 3 3 5 4 3 3 5 4 4 5 For Evaporator Fan Motor Man...

Страница 21: ... fan belt and abnormal sounds Lubrication Compressor The compressors are charged at the factory with the correct oil listed in Component Detailed Data in Technical Catalog Ⅰ and the compressor nameplate It is not necessary to add oil if the cycle remains sealed Fan Motors and Bearings All fan motors and the evaporator fan shaft bearings are pre lubricated Lubrication is not required Refrigerant Cy...

Страница 22: ... period prepare the unit for operation as follows 1 Thoroughly inspect and clean the unit 2 Clean or replace the air filters 3 Clean the condensate drain lines 4 Remove any accumulated dirt from the condenser and the evaporator coil 5 Check the fan balance and attempt to operate the fan 6 Check the fan belt tension 7 Tighten all wiring connections and access panels 9 REPLACEMENT OF PARTS Replaceme...

Страница 23: ... Temperature Superheat 8 Check Pressures Discharge Pressure kg cm2G Suction Pressure kg cm2G 9 Check Voltage Rated Voltage V Operation Voltage R S V S T V T R V Starting Voltage V Phase Imbalance 1 V Vm 10 Check Compressor input and running current Input kW Running Current A 11 Do the control devices function properly 12 Do the protective devices function correctly 13 Is the refrigerant charge ade...

Страница 24: ...place the Contactor Repair the Contacts Replace the Compressor Correct the Wiring No Voltage or Low Voltage Single Phase Shorted Components Loose Connections High Voltage or Low Voltage Single Phase or Phase Imbalance Faulty Fan Bearing Excessive Fan Belt Tension Excessive Fan Load Burned Coil Faulty Contact Defective Operation Switch High Voltage or Low Voltage Single Phase or Phase Imbalance Bur...

Страница 25: ... Suction Pressure Low Discharge Pressure Add Refrigerant See Unit Working Range Operating High Discharge Pressure or Low Suction Pressure Clogged Capillary of Pressure Switch High or Low Pressure Switch Tripped Overcurrent Relay for Compressor Compressor Cycling Insufficient Cooling High Discharge Pressure and High Suction Pressure Loose Connections High Suction Pressure High Discharge Pressure or...

Страница 26: ...tacles to Air Circulation Repair or Replace if Required Remove the Restriction Add Refrigerant See Low Discharge Pressure Noisy Operation Remove the Washers Charge the Correct Refrigerant Quantity See Low Suction Pressure Replace or Repair the Compressor Fix the Runner or Casing Properly Replace the Bearing Adjust Fan Belt Tension Clean the Strainer Add Refrigerant Tighten All Fixed Screws See the...

Страница 27: ...65MP3179 ...

Отзывы: