background image

11

5. Drain Piping

   

Install the drain piping

·

Make sure the drain works properly .
Prepare polyvinyl chloride pipe with a 1-1/4 in.(32mm)

·

    outer diameter.

The diameter of drain pipe connection hole should

·

    be same as that of the drain pipe.

Keep the drain pipe short and sloping down wards 

·

    at a gradient of at least 1/100 to prevent air pockets 
    from forming.

Water accumulating in the drain piping can cause 
the drain to clog.

Refrigerant 
pipes

Bucket

Portable pump

Air outlet

Drain outlet

Installation and Maintenance

CAUTION

CAUTION

·

pip

To keep the drain 

e from sagging, space hanging 

     wires every 3.3 ft. (1m) to 5.0 ft. (1.5m).

Use the drain hose and the clamp. Insert the drain 

·

     hose fully into the drain socket and firmly tighten 
     the drain hose and warm-keeping material with the 
     clamp.  

The two areas below should be insulated because 

·

     condensation may happen there causing water 
     leakage. 

·

Drain piping passing indoors
Drain sockets.

·

Referring the figure below, insulate the drain socket 

·

    and drain hose using the included large sealing pad.

Drain piping connections

Do not connect the drain pipes directly to sewage 

·

    pipes to avoid ammonia odour. The ammonia in the 
    sewage might enter the indoor unit through the drain 
    pipes and corrode  the heat exchanger.

Do not twist or bend the drain hose, doing so applies

·

    excessive force applied on it and may also cause 
    leakage.

After piping work is finished, check if drainage flows

·

    smoothly.

Gradually pour approximately 1000 cc of water from

·

    the outlet hole into the drain pan to check drainage 
    flow.

Check the drainage as shown below:

·

Drain hose

Sealing material

Sealing material

When

 

the

 

relative

 

humidity of inlet or ambient air

exceeds 80%, apply an (field-supplied) auxiliary 
drain pan beneath the indoor unit as shown below.

Indoor Unit

To the Atmosphere

(Field-Supplied)

Auxiliary Drain Pan

Содержание RPIL-1.0PNN1DH

Страница 1: ...HO2021386HA RPIL 1 0PNN1DH RPIL 1 5PNN1DH RPIL 2 0PNN1DH RPIM 3 0PNN1DH RPIM 4 0PNN1DH INDOOR UNITS DC INVERTER SERIES ...

Страница 2: ......

Страница 3: ... Maintenance 1 Safety Notice 6 2 Tools and Instruments for Installation 7 3 Installation of the Indoor Unit 7 3 1 Initial Check 7 3 2 Installation 8 4 Refrigerant Pipe 10 4 1 Pipe Material 10 4 2 10 Piping Connection 5 Drain Piping 11 6 Electrical Wiring 12 6 1 General Check 12 6 2 Change of Static Pressure 13 6 3 Electrical Installation 14 7 Trial Run 14 ...

Страница 4: ...ditioner where excessively high heat generating objects are placed DANGER WARNING If the supply cord is damaged it must be replaced by the factory or its service department in case of danger The place where this product is installed must have the reliable electrical grounding facility and protection Please do not connect the grounding of this product to various kinds of air feeding ducts drain pip...

Страница 5: ...and supply cord is detailed in below part The cord of the H07RN F type or the electrically equivalent type must be used for power connection and interconnection between outdoor unit and indoor unit The size of the cord is detailed in below part The information of dimensions of the space necessary for correct installation of the appliance including the minimum permissible distances to adjacent stru...

Страница 6: ...outlet 1 0HP 9K 1 5HP 12K 2 0HP 18K 3 0HP 24K 4 0HP 36K Remote Controller Optional You can control the air conditioner with the wired controller or remote controller It is used for power ON OFF setting the operation mode temperature fan speed etc There are different types of remote controllers that can be used Operation instruction will be further specified in remote controller s manual Please rea...

Страница 7: ... cases to prevent cold draft After defrosting is over the heating operation and the fan speed resume Blowing out the residual heating air When stopping the air conditioner in normal operation the fan motor might run with low speed for a while to blow out the residual heating air Auto restart from power break When the power supply is recovered after power break all presets are still effective and t...

Страница 8: ...r dust the frequency of cleaning the air filter should be increased Screws Air filter Air inlet flange Remove the fixed screws of the filter and pull the filter down along the rail of the flange as the figure below Clean the air filter with a vacuum cleaner or clean water 1 Use a vacuum cleaner with the air inlet side facing the nozzle of the vacuum 2 Use clean water with air inlet side turning ba...

Страница 9: ...en the indoor and outdoor units Firmly clamp the interconnecting wires so their terminals receive no external stresses Incomplete connections or clamping may cause terminal overheating or fire After connecting all the wires be sure to fix the cables so that they do not put undue force on the electrical covers or panels Install covers over the wires incomplete cover installation may cause terminal ...

Страница 10: ...rd screwdriver Vacuum pump Charge hose Pipe bender Adjustable wrench Pipe cutter Cross head screw driver Number 8 9 10 11 12 13 14 Tool Leveler Hammer Churn drill Knife or wire stripper Pipe expander Inner hexagon spanner Measuring tape 12 300 or more Maintenance space 3 0HP 24K 4 0HP 36K 3 4 20 or more Ceiling H 15 3 4 400 98 1 2 2500 or more Floor surface Fig 3 1 1 unit in mm 1 Reserve necessary...

Страница 11: ...d noise in electrical appliances Noise may be generated depending on the conditions under which the electric wave is generated even if a one meter allowance is maintained Do not install the indoor unit in a machinery shop or kitchen where vapor from oil or its mist flows to the indoor unit The oil will deposit on the heat exchanger thereby reducing the performance of the indoor unit and may deform...

Страница 12: ...pension to prevent the nuts from loosening 1 During the installation please cover the unit with the plastic cloth to keep it clean 2 Make sure that the unit is installed level by using a level or a plastic pipe filled with water in instead of a level adjust the top surface of the unit to the surface of the water at both ends of the plastic pipe and adjust the unit horizontally one thing to watch o...

Страница 13: ...on and Maintenance DANGER The pipe goes through the hole with the seal CAUTION Do not place the pipes on the floor directly Fig 4 3 Tightening torque for the nut Clamp Insulation Refrigerant pipe field supplied Side of the indoor unit Insulation field supplied Fig 4 2 The pipe diameter 1 0HP 9K 1 5HP 12K 2 0HP 18K Ref gas pipe Ref liquid pipe Drain pipe for drain pump Drain pipe 6 9 16 166 5 129 8...

Страница 14: ...nsulated because condensation may happen there causing water leakage Drain piping passing indoors Drain sockets Referring the figure below insulate the drain socket and drain hose using the included large sealing pad Drain piping connections Do not connect the drain pipes directly to sewage pipes to avoid ammonia odour The ammonia in the sewage might enter the indoor unit through the drain pipes a...

Страница 15: ...ctrical Wiring When clamping the wiring use the included clamping material to prevent external pressure being exerted on the wiring connections and clamp firmly While performing wiring work make sure the wiring is proper and does not cause the control box lid to stick up then close the cover firmly When attaching the control lid make sure you do not pinch any wires Outside the indoor unit and outd...

Страница 16: ...m Outdoor unit Indoor unit Terminal Terminal Power connecting cord SI SI L L N N Note Since there may be differences in some model s terminal blocks wiring connection should be done according to letters on the terminal block Please disregard numbers in this case HCWA21NEHH Parameter code Function code Function revise indicator ALARM Static Pressure Setting HCWA21NEHH Press and hold both and button...

Страница 17: ... 194 90 14 7 Trial Run Please perform trial run according to outdoor unit installation manual Model Transmitting Cable Size 1 0HP 4 0HP 9K 36K 4 16AWG Note 1 Follow local codes and regulations when selecting field wires and all the above are the minimum wire size 2 Use copper supply wires 3 When transmitting cable length is longer than 49 ft 15m a larger wire size should be selected 4 Install main...

Страница 18: ......

Страница 19: ......

Страница 20: ...ithout notice in order that Hitachi Johnson Controls Air Conditioning Inc may bring the latest innovations to their customers 2021 Johnson Controls Air Conditioning Inc Hitachi 2021 3 Version A Printed in China Hitachi Johnson Controls Air Conditioning Inc ...

Отзывы: