C A U T I O N

Do not install the indoor units in a flammable environment to avoid a

fire or an explosion.

Check to ensure that the ceiling slab is strong enough. If not strong

enough, the indoor unit may fall down on you.

Do not install the indoor units in a machinery shop or kitchen where

vapor from oil or mist flows to the indoor units. The oil will deposit on

the  heat  exchanger,  thereby  reducing  the  indoor  unit  performance,

and may deform. In the worst case, the oil damages the plastic parts

of the indoor unit.

To avoid any corrosive action to the heat exchangers, do not install

the indoor units in an acid or alkaline environment.

When lifting or moving the indoor unit, use appropriate slings to avoid

damage and be careful not to damage the insulation material on units

surface.

2.1  UNIT INSTALLATION

2.1.1  Factory-Supplied Accessories

Accessory

Qty.

Purpose

Pattern Board 

(Carton Board)

1

For adjusting space of 

false ceiling  opening 

and  position of the unit

Checking Scale

1

Washer with 

Insulation 

 (M10)

4

For unit installation

Washer (M10)

4

Drain Hose

1

For Drain Hose 

Connection

Hose Clamp

1

Pipe insulation

1

For refrigerant 

piping connection

Pipe insulation

1

Cord clamp

2

For fixing remote

 

control switch  wiring, 

louver  sensor and  

insulation of piping

Cord clamp

6

Insulation 

(5Tx50x200)

1

For covering wiring 

connection

Insulation 

(5Tx270x270)

1

For covering drain 

connection

2.1.2  Initial Check 

• Install the indoor unit with a proper clearance around it

paying careful attention of installation direction for the piping,

wiring and maintenance working space, as shown below.

• Provide a service access door near the unit piping

connection area on the ceiling.

(mm)

Service 

Access Door

Service Access 

Door

Piping 

Connection

Drain Piping 

Connection

• Check space between ceiling and false ceiling is enough as

indicated below.

• Check the ceiling surface is flat for the air panel installation

work.

Clearance: 

10-20mm

Unit High 

In False 

Ceiling

Unit HP

A(mm)

RCI-1.0 to 2.5HP

238

RCI-3.0 to 6.0HP

288



  

Opening Of False Ceiling

• Cut out the area for the indoor unit in the false ceiling and

install suspension bolts, as shown below.

20

20

840

760

20

20

760

Dimension of 

opening 860 to 910

(Unit size)

(Dimension of 

suspension bolts)

(mm)

4-12 x 32

Holes

(for suspension bolt)

(Dimension of 

suspension bolts)

840 (Unit size)

Dimension of 

opening 860 to 910

Piping connection 

side

Drain piping 

connection side

4-Positions of 

suspension bolts 

(M10 or W3/8)

(Field-supplied)

• Check to ensure that the ceiling is horizontally level,

otherwise water can not flow  .

• Strengthen the opening parts of the false ceiling.

2.1.3  Installation



  

Mounting of Suspension Bolts

Mount suspension bolts using M10 (W3/8) as size, as shown.

For concrete slab:

150 to 160mm

Insert (100 to 150Kg)

Concrete

Steel

Anchor Bolt (W3/8 or M10)

For steel beam:

Suspension Bolt 

(W3/8 or M10)

I-Beam

2

Содержание RCI-1.0FSKDN1Q

Страница 1: ...6 0FSKDN1Q READ AND UNDERSTAND THIS MANUAL BEFORE USING THE HEAT PUMP AIR CONDITIONER KEEP THIS MANUAL FOR FUTURE REFERENCE ORIGINAL INSTRUCTIONS This manual is exclusively prepared for R410A indoor unit Please read this manual in conjunction with corresponding manual for outdoor unit VRF AIR CONDITIONER INDOOR UNIT HEAT PUMP 待KATO桑提供 二维码后 将附 在此处 ...

Страница 2: ...ovided that these are used in accordance with our instructions following the provisions of Directives as amended Manufacturing number and manufacturing year refer to model Nameplate Notes This declaration becomes invalid if technical or operational modifications are introduced without the manufacturer s consent Johnson Controls Hitachi Air Conditioning Europe SAS is authorized to compile technical...

Страница 3: ...h as spas Places where flammable gases may be generated or circulate Places with a saline acidic or alkaline atmosphere Do not install the unit in places where silicon gas is present Any silicon gas deposited on the surface of the heat exchanger will repel water As a result the condensate water will splash out of the collection tray and into the electrical box Water leaks or electrical faults may ...

Страница 4: ...g connection Insulation 5Tx270x270 1 For covering drain connection 2 1 2 Initial Check Install the indoor unit with a proper clearance around it paying careful attention of installation direction for the piping wiring and maintenance working space as shown below Provide a service access door near the unit piping connection area on the ceiling mm Service Access Door Service Access Door Piping Conne...

Страница 5: ...f Opening Pattern Board for Installation Packing Corrugated Board For ceiling already completed with panels Indoor Unit Attach this side of the scale to the inner side of the opening of the ceiling Attach this side of the scale to the lower side of the unit Indoor Unit Attach this side of the scale to the ceiling Panel Checking Scale Check the height of the ceiling at each corner of the unit Check...

Страница 6: ... performed Check to ensure that the indoor fan and the outdoor fan have stopped before electrical wiring work or a periodical check is performed Protect the wires drain pipe electrical parts etc from rats or other small animals If not protected rats may gnaw at unpro tected parts and at the worst a ire will occur CAUTION Install an ELB Earth Leakage Breaker in the power source line Use twisted shi...

Страница 7: ... M6 Cross Screw 4 For fixing air pane If any of these accessories are not in the package please contact your contractor 6 2 INSTALLATION Check the indoor unit height from the false ceiling surface 12 5 0 Ceiling surface Indoor unit If not adjust the distance by using the checking scale with maintaining the levelness of the indoor unit Removing Air Intake Grille from Air Panel 1 Push both ends of k...

Страница 8: ...ant pipe Refrigerant pipe connections Electrical box Indoor unit Air panel U shaped hook Fixing plate 6 When tightening the long screws to prevent air leakage and to be no gap between the false ceiling surface and the indoor unit the inner circumference of the air panel the position to attach the air inlet grille may be slightly deformed However it is not abnormality 26 12 50 False ceiling Indoor ...

Страница 9: ...anel Remove the tape fixing the wiring connectors on the air panel and pull out them as shown in the figure below Connect them with the wiring connectors on the indoor unit H S P S HB Electrical box Motor wiring for auto louver on air panel connector for low voltage 18 poles white Motor wiring for auto louver on indoor unit Connector for low voltage 18 poles white Condition without air intake gril...

Отзывы: