6 Troubleshooting
Indoor unit
SMGB0135 rev.0 - 06/2020
70
6.2 Indoor unit
Alarms through PC-ARFTE
Alarm
code
Protection
code
Outdoor
unit LED301
Blinking
times
Category
Type of abnormality
Main cause
03
-
Indoor
Transmission Alarm (Not
outdoor unit detected)
Loose, disconnected, broken or short-
circuited connector.
16
-
Indoor
DHW tank thermistor
abnormally (THM
DHWT
)
Loose, disconnected, broken or short-
circuited connector.
71
-
Indoor
Tank over-temperature limit
protection
Failure of control relay.
80
-
Indoor
LCD controller transmission
error
No H-link communication for a continuous
period of 90 seconds between Indoor and
LCD User control by connection wiring
(breaking, wiring error, etc.).
102
P102
2 times
Outdoor unit
LCD controller has no power
Power supply problem or incorrect wiring.
Failure of compressor or PCB.
Pipe clogging, excessive refrigerant, innert
gas mixing, fan motor locking at cooling
operation.
103
P103
3 times
Outdoor unit
Abnormal Low Speed of the
Compressor
Failure of compressor or PCB.
104
P104
4 times
Outdoor unit
Compressor Changeover
Failure (Switching Failure)
Failure of compressor or PCB.
105
P105
5 times
Outdoor unit
Lower Limit of Compressor
Overload
Failure of compressor or PCB.
--
P106
6 times
Outdoor unit
Stoppage by OH Thermistor
High Temperature
Incorrect wiring, disconnected wiring,
broken cable, sensor failure.
Pipe clogging, excessive refrigerant, innert
gas mixing, fan motor locking at cooling
operation.
107
P107
7 times
Outdoor unit
Thermistor Failure: Thermistor
disconnection short circuit
Incorrect wiring, disconnected wiring,
broken cable, sensor failure.
--
P109
9 times
Outdoor unit
Stoppage by Transmission
Error, communication error
Incorrect or disconnected wiring.
PCB failure.
--
P110
10 times
Outdoor unit
Power Supply Voltage Error
Power supply problem or incorrect wiring.
Failure of compressor or PCB.
--
P111
11 times
Outdoor unit
Fan abnormality 1
Failure of fan motor.
Failure of PCB.
112
P112
12 times
Outdoor unit
Fan lock, Fan abnormality 2
Failure of fan motor.
Failure of PCB.
113
P113
13 times
Outdoor unit
EEPROM Error
Failure of PCB.
114
P114
14 times
Outdoor unit
Overvoltage abnormality
Power supply problem or incorrect wiring.
Failure of compressor or PCB.
115
P115
15 times
Outdoor unit
Circuit abnormality
Failure of PCB.
--
P116
16 times
Outdoor unit
Software Ip cut stop
Failure of compressor or PCB.
204
-
LCD
Indoor unit stops answering to
PC-ARFTE
Loose, disconnected, broken or short-
circuited connector.
205
-
LCD
Central Alarm, no Central
message
Loose, disconnected, broken or short-
circuited connector.
Содержание RAW-35RHC
Страница 1: ...YUTAMPO SERIES Indoor unit YUTAMPO TAW 190 270 RHC Outdoor unit RAW 35RHC Service Manual ...
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 22: ......
Страница 44: ...4 1 Outdoor unit 4 1 1 Power circuit 4 Electrical checks of main parts Outdoor unit SMGB0135 rev 0 06 2020 36 ...
Страница 58: ......
Страница 88: ......
Страница 93: ......