3 General data
Electrical data
TCGB0136 rev.1 - 05/2021
46
3.5.1 UTOPIA series
Main unit power
Applicable
voltage
Unit data
CB
(A)
ELB
(N°. of
poles/A/
mA)
Outdoor unit
U (V)
PH
f
(Hz)
U
max
(V)
U
min
(V)
STC
(A)
Cooling
Heating
MC
(A)
Max.
IPT
(kW)
RNC
(A)
IPT
(kW)
RNC
(A)
IPT
(kW)
RAS-3HVRC2
230
1
50
253
207
-
7.6
1.67
8.1
1.79
15.8
3.5
20
2/40/30
RAS-4HVRC2E
12.4
2.56
12.8
2.65
22.5
4.6
25
RAS-5HVRC2E
16.3
3.38
17.0
3.52
22.5
4.6
25
RAS-6HVRC2E
21.1
4.38
17.6
3.64
22.5
4.6
25
RAS-4HVNC2E
13.8
2.86
12.6
2.60
22.5
4.6
25
RAS-5HVNC2E
18.3
3.78
17.0
3.52
22.5
4.6
25
RAS-6HVNC2E
23.7
4.91
17.6
3.64
22.5
4.6
25
RAS-4HVRP2E
12.1
2.51
12.6
2.60
22.5
4.6
25
RAS-5HVRP2E
16.5
3.42
16.4
3.39
22.5
4.6
25
RAS-6HVRP2E
21.1
4.38
17.6
3.64
22.5
4.6
25
RAS-4HVNP2E
13.6
2.81
12.4
2.56
22.5
4.6
25
RAS-5HVNP2E
18.5
3.83
16.4
3.39
22.5
4.6
25
RAS-6HVNP2E
23.7
4.91
17.6
3.64
22.5
4.6
25
RAS-4HNC2E
400
3
50
440
360
-
4.9
2.86
4.4
2.60
15
6.7
20
4/40/30
RAS-5HNC2E
6.4
3.78
6.0
3.52
15
6.7
20
RAS-6HNC2E
8.3
4.91
6.2
3.64
15
6.7
20
RAS-4HRC2E
4.4
2.56
4.5
2.65
15
6.7
20
RAS-5HRC2E
5.7
3.38
6.0
3.52
15
6.7
20
RAS-6HRC2E
7.4
4.38
6.2
3.64
15
6.7
20
RAS-4HRP2E
4.3
2.51
4.4
2.60
15
6.7
20
RAS-5HRP2E
5.8
3.42
5.8
3.39
15
6.7
20
RAS-6HRP2E
7.4
4.38
6.2
3.64
15
6.7
20
RAS-4HNP2E
4.8
2.81
4.3
2.56
15
6.7
20
RAS-5HNP2E
6.5
3.83
5.8
3.39
15
6.7
20
RAS-6HNP2E
8.3
4.91
6.2
3.64
15
6.7
20
?
N O T E