![Hitachi RAS-4HNC2E Скачать руководство пользователя страница 41](http://html.mh-extra.com/html/hitachi/ras-4hnc2e/ras-4hnc2e_technical-catalogue_140504041.webp)
3 General data
General specifications
TCGB0136 rev.1 - 05/2021
33
3
3.2
General specifications
UTOPIA Prime with R32 refrigerant for single phase units
OUTDOOR UNITS
RAS-3HVRC2
RAS-4HVRC2E
RAS-5HVRC2E
RAS-6HVRC2E
Power supply
-
1~ 230V 50Hz
1~ 230V 50Hz
1~ 230V 50Hz
1~ 230V 50Hz
Nominal cooling capacity
kW
7.1
10.0
11.9
14.0
Nominal heating capacity
kW
8
11.2
14.0
16.0
Minimum - Maximum connectable
indoor units
-
1 - 2
1 - 4
1 - 4
1 - 4
Minimum - Maximum connected
capacity
%
90% - 100%
90% - 115%
90% - 115%
90% - 115%
Noise level cooling (sound pressure)
(night mode)
dB(A)
54 (48)
54 (51)
54 (51)
56 (51)
Noise level heating (sound pressure)
dB(A)
52
54
54
56
Noise level (sound power)
dB(A)
69
70
70
72
Air flow (cooling / heating)
m
3
/min
45
80
80
80
Dimensions (H x W x D)
mm
629 x 799(+95) x 300 1140 x 950 x 370 1140 x 950 x 370 1140 x 950 x 370
Net weight
kg
48
84
84
84
Recommended circuit breaker
A
20
25
25
25
Maximum current
A
15.8
22.5
22.5
22.5
Running current cooling
A
7.6
12.4
16.3
21.1
Running current heating
A
8.1
12.8
17.0
17.6
Size of power cable (according to EN
60335-1)
quantity x
mm
2
3 x 4.0
3 x 6.0
3 x 6.0
3 x 6.0
Size of transmission cable between
indoor unit and outdoor unit
quantity x
mm
2
2 x 0.75
2 x 0.75
2 x 0.75
2 x 0.75
Piping diameter (liquid / gas)
mm (inch)
Ø9.52 (3/8) /
Ø15.88 (5/8)
Ø9.52 (3/8) /
Ø15.88 (5/8)
Ø9.52 (3/8) /
Ø15.88 (5/8)
Ø9.52 (3/8) /
Ø15.88 (5/8)
Minimum piping length
m
5
5
5
5
Maximum piping length (chargeless)
m
20
20
20
20
Maximum piping length
m
50
75
75
75
Height difference (higher OU / lower OU)
m
30 / 20
30 / 20
30 / 20
30 / 20
Refrigerant
-
R32
R32
R32
R32
Refrigerant charge before shipment
kg
1.7
3
3
3
Additional refrigerant charge needed
g/m
45
45
45
45
Compressor type
-
Rotative DC
Inverter driven
Rotative DC
Inverter driven
Rotative DC
Inverter driven
Rotative DC
Inverter driven