11.2 CarrY oUt tHe test rUn
•
Check that the stop valves on the outdoor unit are fully open
(gas, low-pressure: only in heat recovery systems) and start
the system. (Where base units are combined, check that the
stop valves on all outdoor units connected are fully open).
• Carry out the test run on the indoor units in sequence, one
by one. Then check the concordance of the refrigerant pipe
system and the electrical wiring system. (System conformity
cannot be checked if there are several indoor units operating
at the same time.)
•
Follow the procedure indicated below to carry out the test
run. Make sure the test run is completed problem-free.
?
n o t e
Where there are two remote controls (main and secondary), first carry out
the test run using the main remote control.
11.3 test rUn ProCeDUre BY remote Control sWitCH (PC-arfPe eXamPle)
1
Turn ON the power supply for all the indoor units.
2
For the models with the auto-address function, wait for 3
minutes approximately. The addressing is automatically
performed. (There is a case that 5 minutes is required according
to the setting condition.) After that, select using language from
“Menu”. Refer to the operation manual for details.
3
Press and hold “ ” (menu) and “ ” (return) simultaneously for
at least 3 seconds.
A/C
COOL
HIGH
LOUV.
ADJ
Meeting Room
MODE SPEED LOUV.
TEMP
FLTR
Motion Sensor is activated
OK
?
test run screen
a.
The test run menu will be displayed.
ADJ
/
OK
Test Run Menu
Test Run
Function Selection
Thermistor Selection
Input/Output
Function 5
01
03
ENT.
RTN.
SEL.
b.
Select “Test Run” and press “OK”. The test run settings will
be displayed.
Test Run Setting: 2 units
MODE
SPEED
MED
LOUV.
SEL.
ADJ
T-RUN TIME 120MIN
COOL
RTN.
RUN
?
n o t e
When “00” is indicated, the auto-address function may be performing.
Cancel “Test Run” mode and set it again.
Test Run Setting: 00 unit
MODE
SPEED
MED
LOUV.
SEL.
ADJ
T-RUN TIME 120MIN
COOL
RTN.
RUN
4
The total number of the indoor units connected is indicated
on the LCD (liquid crystal display). The case of the twin
combination (one (1) set with two (2) indoor units) is indicated
“2 units”, and the triple combination (one (1) set with three (3)
indoor units) is indicated “3 units”.
Test Run Setting: 2 units
MODE
SPEED
MED
LOUV.
SEL.
ADJ
T-RUN TIME 120MIN
COOL
RTN.
RUN
a.
If the indicated number is not equal to the actual connected number of indoor unit, the auto-address function is not performed
correctly due to incorrect wiring, the electric noise or etc. Turn OFF the power supply and correct the wiring after checking the
following points; (Do not repeat turning ON and OFF within 10 seconds.)
ENGLISH
COMMISSIONING
PMML0479 rev.4 - 11/2018
45
Содержание RAS-10FSXNPE
Страница 2: ......
Страница 14: ... i RAS 8 12 FSXNSE 1725 959 784 B A ...
Страница 15: ... RAS 14FSXNSE 1725 1219 784 B A ...
Страница 16: ... RAS 16 18 FSXNSE 1725 1219 784 B A ...
Страница 17: ... RAS 20 24 FSXNSE 1725 1609 784 B A ...
Страница 18: ... RAS 5 6 FSXNPE 1725 959 784 A B ...
Страница 19: ... RAS 8 14 FSXNPE 1725 1219 784 A B ...
Страница 20: ... RAS 16 18 FSXNPE 1725 1609 784 A B ...
Страница 119: ......
Страница 169: ......