First branch
outdoor unit HP
model
5-10
E-102SN4
12-16
E-162SN4
18-24
E-242SN3
26-54
E-302SN3
56-96
MW-NP2682A3
Ⓒ
Multi-Kit after first branch
total indoor unit HP
model
<12
E-102SN4
12-17.99
E-162SN4
18-25.99
E-242SN3
26-55.99
E-302SN3
≥ 56
MW-NP2682A3
Ⓓ
Header branch
total indoor unit HP
number of header
branches
model
5-8
4
E-102SN4
5-10
8
E-162SN4
Diameter of the main pipe (from the base of the unit or
connection kit 1 to the first branch).
outdoor unit (HP)
equivalent pipe length < 100 m
Gas
liquid
5
ø15.88
ø9.52
(6/8)
ø19.05
ø9.52
10
ø22.20
ø9.52
(12/14)
ø25.40
ø12.70
16
ø28.58
ø12.70
(18-24)
ø28.58
ø15.88
(26-34)
ø31.75
ø19.05
(36-54)
ø38.10
ø19.05
(56-66)
ø44.45
ø19.05
(68-72)
ø44.45
ø22.20
(72-88)
ø50.80
ø22.20
≥ 90
ø50.80
ø25.40
?
n o t e
When the maximum length of the equivalent refrigerant pipe from the
piping connection kit 1 to the indoor unit is over 100m, the pipe size of gas
and liquid lines from the piping connection kit 1 to first branch should be
increased by one size with reducers (field-supplied).
Pipe diameter after first branch or between Multi-Kits in the
main branch.
total indoor unit capacity after the
first branch (HP)
Gas
liquid
< 6
ø15.88
ø9.52
(6-8.99)
ø19.05
ø9.52
(9-11.99)
ø22.20
ø9.52
(12-15.99)
ø25.40
ø12.70
(16-17.99)
ø28.58
ø12.70
(18-25.99)
ø28.58
ø15.88
(26-35.99)
ø31.75
ø19.05
(36-55.99)
ø38.10
ø19.05
(56-67.99)
ø44.45
ø19.05
(68-73.99)
ø44.45
ø22.20
(74-89.99)
ø50.80
ø22.20
≥ 90
ø50.80
ø25.40
?
n o t e
• In the case that the piping length from the Multi-Kit at the first branch
to the terminal indoor unit is over 40m, the size of the main piping
should be increased by one size with reducers (field-supplied). Refer
to “Piping Branch Restriction” for details.
• Even if the equivalent refrigerant piping length is more than 100m, no
need to increase the pipe size after first branch. If the Multi-Kit size is
larger than the first branch, adjust the Multi-Kit size to the first branch.
In case that the selected pipe size after the first branch is larger than
the pipe size before the first branch, use the same pipe size as before
the branch.
Pipe diameter between Multi-Kit and indoor unit.
indoor unit (HP)
Gas
liquid
(0.4-1.5)
ø12.70
ø6.35(*)
2.0
ø15.88
ø6.35(*)
(2.5-6.0)
ø15.88
ø9.52
8.0
ø19.05
ø9.52
10.0
ø22.20
ø9.52
16.0
ø28.58
ø12.70
20.0
ø28.58
ø15.88
?
n o t e
• (*): When the liquid piping length is longer than 15m, use ø9.52 pipe
and reducer (field-supplied).
• The pipe diameter should be the same as the indoor unit piping
connection size.
• Check the corresponding Indoor unit connection sizes.
ENGLISH
PIPING WORK AND REFRIGERANT CHARGE
PMML0479 rev.4 - 11/2018
13
Содержание RAS-10FSXNPE
Страница 2: ......
Страница 14: ... i RAS 8 12 FSXNSE 1725 959 784 B A ...
Страница 15: ... RAS 14FSXNSE 1725 1219 784 B A ...