– 31 –
heatly
Notes:
(1) 30 seconds after the operation is started, when the room temperature is (cooling preset temperature) - (1.33˚C) or less, the operation is
done assuming as the preset temperature = (room temperature at the time) - (2˚C).
(2) The indoor fan is operated in the “Lo” mode, OFF for 5 minutes and ON for 1 minule (at high humidity) or OFF for 6 minutes and ON for
1 minute (at low humidity), repeatedly acoording to the humidity judgement when the thermostat is turned OFF.
(3) When the operation is started by the themostat turning ON, the start of the indoor fan is delayed 32 seconds after the start of compressor
operation.
(4) The compressor is operated forcedly for 3 minutes after operation is started.
(5) The minimum ON time and OFF time of the compressor are 3 minutes.
Содержание RAM-35QH5
Страница 9: ... 8 ...
Страница 10: ... 9 MODEL RAM 40QH5 ...
Страница 11: ... 10 ...
Страница 12: ... 11 AC 220V 240V ONLY L N INDOOR 1 C1 D1 C2 D2 INDOOR 2 ...
Страница 13: ... 12 ...
Страница 21: ... 20 MODEL RAM 40QH5 WIRING DIAGRAM OUTDOOR UNIT ...
Страница 23: ...PRINTED WIRING BOARD LOCATION DIAGRAM MODEL RAM 40QH5 23 MOUNTING PCB SET TYPE ...
Страница 25: ... 27 heating ff BASIC MODE MODEL RAM 40QH5 ...
Страница 28: ... 33 Table 6 Table 7 ...
Страница 29: ... 35 ...
Страница 31: ... 37 ...
Страница 56: ... 62 Fig 11 2 ...
Страница 69: ... 75 1 Outdoor unit does not operate remote control signal can be received RAM 40QH5 ...
Страница 71: ... 77 Lighting mode self diagnosis lamp 2 RAM 40QH5 ...
Страница 72: ... 78 TROUBLESHOOTING OF THE SYSTEM POWER MODULE ...
Страница 73: ... 79 ...
Страница 74: ... 80 ...
Страница 75: ... 81 ELECTRIC EXPANSION VALVE PIPE THERMISTOR POSITION CHARTS MODEL RAM 40QH5 ...
Страница 78: ...HITACHI PM NO 0270E Printed in Malaysia RAM 40QH5 ...