Removal Of Air From The Pipe And Gas Leakage Inspection

FINAL

 ST

AGE OF INST

ALLA

TION

Insulation And Maintenance Of Pipe Connection

1

 The connected terminals should be completely sealed with heat insulator and then tied up with rubber 

strap.

 Please tie the pipe and power line together with vinyl tape as shown in the 

fi

 gure showing the installation 

of Indoor and Outdoor units. Then 

fi

 x their position with holders.

 To enchance the heat insulation and to prevent water condensation, please cover the outdoor part of 

the drain hose and pipe with insulation pipe.

 Completely seal any gap with putty.

  Power Source And Operation Test

3

Power Source

CAUTION

!

 Please use a new socket. Accident may occur due to the use of old socket because of poor contact.

 Please plug in and then remove the plug for 2 – 3 times. This is to ensure that the plug is completely 

plugged into the socket.

 Keep additional length for the power cord and do not render the plug under external force as this 

may cause poor contact.

 Do not 

fi

 x the power cord with U-shape nail.

3

Procedures of using Vacuum Pump for Air Removal

As shown in right 

fi

 gure, remove the cap of valve core. Then, connect the charge hose. 

Remove the cap of valve head. Connect the vacuum pump adapter to the vacuum pump 
and connect the charge hose to the adapter.

Fully tighten the “Hi” knob of the manifold valve and completely unscrew the “Lo” knob. 
Run the vacuum pump for about 10~15 minutes, then completely tighten the “Lo” knob 
and switch off the vacuum pump.

Remove the charge hose and tighten the cap of valve core. Check the cap’s periphery 
if there is any gas leakage. 

Completely unscrew the spindle of the service valve (at 2 places) in anti-clockwise 
direction to allow the 

fl

 ow of refrigerant (using Hexagonal Wrench key).

Re-cap the service valve and tighten using wrench. Check the cap’s periphery if there 
is any gas leakage. The task is then completed.

   Preparation of Pipe

1

 Use a pipe cutter to cut 

  the copper pipe.

   Pipe Connection

2

INST

ALLA

TION OF REFRIGERA

TING PIPES 

AND 

AIR REMOV

AL

AIR REMOV

AL

Checking for the electric 
source and the voltage range

 Before installation, the power source must be checked 

and necessary wiring work must be completed. To make 
the wiring capacity proper, use the wire gauges list below 
for the lead-in from a pole transformer and for the wiring 
from a switch board of fuse box to the main switch and 
outdoor unit in consideration of the locked rotor current.

 THIS APPLIANCE MUST BE 

EARTHED.

Procedures of Wiring

In case that power is supplied from Indoor Unit

CONNECTION OF POWER CORD

!

 Recommend to use 

R410A 

fl

 aring  tool.

CAUTION

!

In case of removing 

fl

 are nut of an Indoor 

unit, 

fi

 rst remove a nut of small diameter 

side, or a seal cap of big diameter side will 

fl

 y out. Prevent water from entering into the 

piping when working.

Wiring Of The Indoor Unit

  For wire connection of the Indoor unit, you need to 

remove front panel and electrical cover.

Method to remove front panel

  Refer to “FINAL STAGE OF INSTALLATION – How to 

Remove The Front Cover”.

Power supply shall be connected at the rated voltage, otherwise the 
unit will be broken or could not reach the speci

fi

 ed  capacity.

 Jagged edge will cause leakage.

 Point the side to be trimmed downwards during trimming 

to prevent copper chips from entering the pipe.

 Before 

fl

 aring, please put on the 

fl

 are  nut.

CAUTION

!

1

2

3

4

5

Gas Leakage Inspection

Please use gas leakage detector to check if leakage occurs 
at the connection of Flare nut as shown on the right.

If gas leakage occurs, further tighten the connection to stop 
leakage. (Use the detector provided for R410A).

GRN + YEL

Strip wires

 The naked part of the wire core should be 10 mm and 

fi

 x  it 

to the terminal tightly. Then try to pull the individual wire to 
check if the contact is tight. Improper insertion may burn the 
terminal.

  Be sure to use only power cables approved from the authorities 

in your country. For example in Germany: Cable type: NYM 
3x1.5mm2.

 Please refer to the installation manual for wire connection to 

the terminals of the units. The cabling must meet the standards 
of electrical installation.

 There is a AC voltage of 230V between the L and N terminals. 

Therefore, before servicing, be sure to remove the plug from 
the AC outlet or switch off the main switch.

WARNING

!

IMPORTANT

Cable length

up to 

1

6m

up to 15m

up to 25m

Wire cross-section

1.5mm

2

2.5mm

2

4.0mm

2

Indoor Unit

Connect the
earth cord

Method to remove the low cover

 Pull the cover at   and   in the directions as 

shown by arrows to remove the cover.

After remove the screw 
and cover, and put the 
connecting cords and 

fi

 x 

the cover with screw.

How to Remove The Front Cover

 1  Remove the front panel.

 

Please remove and attach the front panel by both hands.

 

After opening the front panel by both hands.

  Undo the right arm while pushing it inside.
  Slide the front panel to right as shown in 

fi

 gure. Then remove while 

pulling it to front.

  Open the electrical cover. Disconnect the wire connector.

 2  Remove the 

fi

 lters.

  3  After removing two screws, pull the center of the front cover towards 

you and release the claws.

 4  Pull the side faces (lower sections) of the front cover towards you 

as shown in the 

fi

 gure and remove the cover.

How to Attach the Front Cover

Check that the drain pan is securely attached.

2  After installing the front cover onto the unit, hook three 

claws at upper side of the cover securely. Then, push 
the center of the front cover to lock the claws.

Tighten the two screws.

Connect the wire connector. Close the electrical cover.

5 Install 

the 

fi

 lter.

Slide the shafts of the right and left arms on the washable 
panel along the steps to insert the shafts into the holes 
till they stop. After checking that the shafts are securely 
inserted, close the panel.

/R

+L

[For all optional part, please refer catalog for part number]

As for connecting to H-Link, a separately purchased 
RAC Adapter is required.

  To install the wiring the electrical box cover must be opened.

 Connect the connector of RAC adapter to CN7.

 Assemble back the cover of electrical box.

 Please refer to the respective user manual of RAC Adapter 

for further details.

 Please be careful not to damage lead wires by edge of 

plate when connecting the optional parts.

[For all optional part, please refer catalog for part number]

Connection to the electrical box:

 Remove the cover of electrical box.

 Connect the connector of wired remote controller to CN9.

 Assemble back the cover of electrical box.

 Please refer to the respective user manual of wired remote 

controller for further details.

 Please be careful not to damage lead wires by edge of 

plate when connecting the optional parts.

WIRED REMOTE CONTROLLER

H-LINK

How To Connect The Optional Parts

(RAC Adapter, Wired Remote Control)

RAC Adapter cord

Fix the wired remote controller cord and RAC 
adapter cord by band.

Wired remote 
controller cord

Locking mechanism

 

To remove the front panel, 
slide the front panel locking 
mechanisms (left and right) 
toward the directions as 
indicated by arrows in the 
illustration, until you hear a 
clicking sound.

 

Remove the front 
panel by pulling it 
towards you.

Arm

Step

Slot

 

Firmly insert the front 
panel arms by sliding 
along the steps located 
at the main body

 

Slide the front panel 
locking mechanisms 
(left and right) into the 
slots located at the 
main body, until you 
hear a clicking sound.

Slot

Disconnect the wire connector

Terminal cover

Push to lock the claws

  Installation Of Remote Controller

2

 The remote controller can be placed in its holder 

which is 

fi

 xed on wall or beam.

  To operate the remote controller at its holder, please 

ensure that the unit can receive signal transmitted 
from the controller at the place where the holder 
is to be 

fi

 xed. The unit will beep when signal is 

received from the remote controller. The signal 
transmission is weaken by the 

fl

 uorescent  light. 

Therefore, during the installation of the remote 
control holder, please switch on the light, even 
during day time, to determine the mounting location 
of the holder.

Operation Test

 Please ensure that the air conditioner is in normal operating condition during the operation test.

 Explain to your customer the proper operation procedures as described in the user’s manual.

Front Panel

Trimming tool

Copper pipe

Die

Die

Copper pipe

30mm

10mm

10mm

70mm

Insulation material for pipe connection

Flare nut

Torque
wrench

Wrench

RAC Adapter

Wired remote controller

Putty

Putty

Sleeve of 
protection pipe

Cap of valve head

Cap of valve head

The body of 
service valve

Hexagonal 
Wrench Key

Cap of valve 
core

When pumping starts, 
slightly loosen the 

fl

 are 

nut to check of air 
sucked in. Then tighten 
the 

fl

 are  nut.

Vacuum pump adapter

Vacuum pump

Stop 
valve

Stop 
valve

R410A Manifold 
valve

Charge hose

Closed

Meter showing pressure

When the meter reaches -101KPa 
(-76cmHg) during pumping, fully tighten 
the shuttle.

<

IA1008: A 

>

Outer

dia.of pipe

6.35 (1/4")

9.52 (3/8")

12.70 (1/2")
15.88 (5/8")

6.35 (1/4")

9.52 (3/8")
12.7 (1/2")

Valve 

head cap

Torque N·m

(kgf 

·

 cm)

14.0 – 18.0 (140 – 180)

33.0 – 42.0 (330 – 420)
50.0 – 62.0 (500 – 620)
63.0 – 77.0 (630 – 770)

19.6 – 24.5 (200 ~ 250)

19.6 – 24.5 (200 ~ 250)
29.4 – 34.3 (300 – 350)

12.3 – 15.7 (125 ~ 160)

Small dia. side

Large dia. side

Valve core cap

Small dia. side

Large dia. side

Outer
Diameter (mm)

6.35 (1/4)

9.52 (3/8)

12.70 (1/2)

15.88 (5/8)

1.0~1.5

1.0~1.5

1.0~1.5

1.0~1.5

Clutch type

A (mm)

1.5~2.0

1.5~2.0

1.5~2.5

1.5~2.5

Wing nut type

Thickness

(mm)

0.8

0.8

0.8

1.0

0.0 

~

 0.5

0.0 

~

 0.5

0.0 

~

 0.5

0.0 

~

 0.5

Flare tool for R410A

Clutch type

Conventional 

fl

 are  tool

The remote 
controller must be 
slide in
the remote 
controller holder, 
in the direction 
as shown in the 

fi

 gure, until it 

hooks at the lower 
end of the remote 
controller holder.

Screw (2 pieces)

Remote 
Controller 
Holder

Remote
Controller

WARNING

INS RAK-25-35-50QXA (EN).indd   2

1/17/13   4:33 PM