background image

Please mount the Outdoor unit of stable ground to prevent vibration and increase
of noise level.

Decide the location for piping after sorting out the different types of pipe available.

When removing side cover, please pull the handle after undoing the hook by pulling
it downward. Reinstall the side cover in the reverse order of the removal.

CONDENSED WATER DISPOSAL OF OUTDOOR UNIT

There is holes on the base of Outdoor unit for condensed water to exhaust.

In order to flow condensed water to the drain, the unit is installed on a stand or a
block so that the unit is 100mm above the ground as shown figure.  Join the drain
pipe to one hole.

After installation, check whether the drain pipe clings to the base firmly.

Install the outdoor unit horizontally and make sure that condensate drains away.

In case of using in chilly area
Especially, in case that there are many snows by very cold in chilly area, condensed
water freezes on the base and may result not to drain.  In this case, please remove
the bush and the drain pipe at the bottom of unit.  (Left and center near discharge
portion of air, each 1 place).  It becomes smooth drain.
Ensure that the distance from the drain hole to the ground is 250 mm or more.

 CAUTION

Remove burr and jagged edge will cause leakage.

Point  the  side  to  be  trimmed  downwards  during  trimming  to  prevent  copper
chips from entering the pipe.

Copper pipe

Trimming tool

Before flaring, please put on the flare nut.

A

Die

Die

Copper pipe

Please use
exclusive tool for
refrigerant R410.

2 Pipe Connection

 CAUTION

In case of removing flare nut of a indoor unit, first remove

a nut of small diameter side, or a seal cap of big diameter

side  will  fly  out.  Free  from  water  into  the  piping  when

working.

Be sure to tighten the flare nut to the specified torque with

a torque wrench.

If the flare nut is overtightened, the nut may be split after a

long period has passed, and may cause a refrigerant  leak.

Please be careful when bending the copper pipe.

Screw  in  manually  while  adjusting  the  center.  After  that,  use  a  torque  wrench  to
tighten the connection.

O

ME

RI

D

N

SE

PI

G

NI

TA

RE

GI

RF

E

F

N

OI

TA

LL

AT

S

NI

L

AV

Torque
wrench

Flare nut

Wrench

3 Remove of Air From The Pipe And Gas Leakage Inspection

L

AV

O

M

E

RI

A

Procedures of using Vacuum Pump for Air Removal

As shown in right figure, remove the cap
of valve core.  Then, connect the charge
hose.  Remove  the  cap  of  valve  head.
Connect the vacuum pump adapter to the
vacuum  pump  and  connect  the  charge
hose to the adapter.

1

Fully tighter the "Hi" shuttle of the manifold
valve  and  completely  unscrew  the  "Lo"
shuttle.  Run the vacuum pump for about
10-15 minutes, then completely tighten the
"Lo"  shuttle  and  switch  off  the  vacuum
pump.

Loosen the spindle of the service valve
with  small  diameter  by  1/4  turn  and
tighten the spindle immediately after 5
to 6 seconds.

Remove  the  charging  hose  from  the
service valve.

2

Completely  unscrew  the  spindle  of  the
service valve (at 2 places) in anticlockwise
direction  to  allow  the  flow  of  refrigerant
(using Hexagonal Wrench key).

3

Tighten the cap of valve head.  Check the
cap's periphery if there is any gas leakage.
The task is then completed.

4

The body of service

valve

Cap of
valve core

Hexagonal wrench Key

Cap of valve
head

   Gas leakage inspection

Please use gas leakage detector to check if leakage occurs  at

  connection  of  Flare  nut  as  shown  on  the right.

If gas leakage occurs, further tighten the connection to stop leakage.

D

R

O

R

E

W

O

F

N

OI

T

C

E

N

N

O

C

 WARNING

TI

N

R

O

O

D

T

U

O

N

OI

T

A

L

L

AT

S

NI 

F

E

G

AT

L

A

NI

F

1 Preparation of Pipe

Use a pipe cutter to cut the copper pipe and remove burr.

Power Source And Operation Test

Power Source

 WARNING

Never remodel the power plug nor extend the long-distance
cord.

Keep additional length for the power cord and do not render
the plug under external force as this may cause poor contact.

Do not fix the power cord with U-shape nail.

The power cable easily generates heat. Do not bring the
cable together with a wire or vinyl tie.

Operation test

Please  ensure  that  the  air  conditioner  is  in  normal  operating
condition during the operation test.

Explain to your customer the proper operation procedures as
described in the user' s manual.

If  the  indoor  unit  won't  operate,  check  the  cable  for  correct
connection.

Turn on the lamp in the room where the indoor unit is installed
and check the remote controller for normal operation.

How to remove the front cover

How to Attach the Front Cover

Check that the drain pan is securely attached.

After installing the front cover onto the unit, hook three claws
at upper side of the cover securely. Then, push the center of
the front cover to lock the claws.

Tighten the two screws.

Install the filter.

Slide the shafts of the right and left arms on the front panel
along the steps to insert the shafts into the holes till they stop.
After checking that the shafts are securely inserted, close the
panel.

Remove the front panel

Please remove and attach the front panel by both hands.

After opening the front panel by both hands.
Undo the right arm while pushing it inside.
Slide the front panel to right as shown in figure. Then remove
while pulling it to front.

Remove the filters.

After removing two screws, pull the center of the front cover
towards you and release the claws.

Pull the side faces (lower sections) of the front cover towards
you as shown in the figure and remove the cover.

WARNING

THIS APPLIANCE MUST BE
EARTHED.

Procedures of Wiring

Cap of valve
head

 CAUTION

Do  not  touch  the  suction
port,  bottom  surface,  or
aluminum fin of the outdoor
unit.
Failure to do so may cause
an injury.

 WARNING

Leave  some  space  in  the  connecting  cord  for  maintenance
purpose and be sure to secure it with the cord band.

Secure  the  connecting  cord  along  the  coated  part  of  the  wire
using the cord band. Do not exert pressure on the wire as this
may cause overheating or fire.

Indoor Unit

Outdoor Unit

WARNING

If you cannot attach the side plate due to the connection cord, please
press the connecting cord in the direction to the front panel to fix it.

Be sure that the hooks of the side cover fixed in certainly. Otherwise water
leakage may occur and this causes short circuit or faults.

The  connecting  cord  should  not  touch  to  service  valve  and  pipes.  (it
becomes high temperature in heating operation.)

Wiring of the Outdoor Unit

Please remove the side cover for wire connection.

Checking for the electric source and the voltage range

Before installation, the power source must be checked and necessary wiring work must
be completed. To make the wiring capacity proper, use the wire gauge list below for the
wiring from house distribution fuse box to the outdoor unit in consideration of the blocked
rotor current.

Investigate  the  power  supply  capacity  and  other
electrical conditions at the installing location.
Depending on the model of room air conditioner to be
installed, request the customer to make arrangements
for the necessary electrical work etc.
The  electrical  work  includes  the  wiring  work  up  the
outdoor  unit.  In  localities  where  electrical  conditions
are poor, use of a voltage regulation is recommended.

Install outdoor for the room air conditioner within the
reaching range of the line cord.

IMPORTANT

Fuse Capacity

1 A time delay fuse

Force-cooling operation

When the service switch of the outdoor unit is pressed for 1
or more seconds, the force-cooling operation starts. Use this 
mode when performing the failure diagnosis or collecting 
refrigerant into the outdoor unit.

 CAUTION

Do not operate the unit for more than 5 minutes
while the spindle of the service valve is closed.

Push up the [PUSH] sections at the bottom of the indoor unit and
pull the bottom plate towards you. Then the claws are released
from the stationary plate.
(The [PUSH] sections are indicated by 2 arrows in the right figure)

HOW TO REMOVE INDOOR UNIT

[PUSH] mark positions

After completing the service switch
operation, be sure to keep the
switch pressed for one or more
seconds and stop the force-cooling
operation.

Service switch (If the switch is pressed for one
or more seconds, the force-cooling operation
starts. If the switch is pressed for additional
one or more seconds, the operation stops.)

Wiring of The Indoor Unit

For wire connection of the Indoor unit, you need to remove the front cover, the low cover
under the body of the unit and terminal cover.

Please remove side cover.

The naked part of the wire core should be 10mm fix it to the terminal tightly. Then
try to pull the individual wire to check if the contact is tight. Improper insertion may
burn the terminal.

Be sure to use only wire specified for the use of air-conditioner.

Please refer to the manual for wire connection and the wiring technique should
meet the standard of the electrical installation.

There is an AC voltage drop between the LN terminal if the power is on. Therefore,
be sure to remove the plug from its socket.

For  cable  connection  to  control  P.W.B.,  you  need  to
remove front cover and electrical box cover.

    Each connecting location is as below.

1

 

2

 

3

 

Wired Remote Control  : CN20

Please  check  and  confirm  manuals  attached  to  each
optional parts for more connection details.

You can refer to this installation manual how to remove
and re-attach the front cover.

Please be careful not to damage lead wires by edge of
plate when connecting the optional parts.

Remove the cover from the terminal base and screw the cable.

Method to remove the low cover

Pull at the 

1

 and 

2

 in

the directions as shown
by arrows to remove the
cover.

5

ler

above

BASE

Outer diameter: 

16 mm or more

When the meter reaches - 101KPa
(-76cmHg)  during  pumping  fully
tighten the shuttle.

Meter showing
pressure

Closed

R410A

Manifold

valve

Vacuum

pump

Valve

Charge
hose

Vacuum

pump

adapter

When  pumping  starts,  slightly

loosen the flare nut to check of

air sucked in.  Then tighten the

flare nut.

Valve

70mm

Please face this side (suction side)
of the unit to the wall.

Please remove terminal cover
when connecting the piping
and connecting cord.

Pull downward

L N

Connecting Cord

AC 220-230V
1ø 50Hz

1  2  3

1  2  3

Detail of Cutting the Connecting Cord

CN7

CN20

CN6

CN6

CN7

CN21

 cover

Cord band

Screw

Earth terminal

7  DRAIN PIPE

160mm

10mm

100mm

 

1

2
3

70mm

10mm

10mm

45mm

1

2

3

Connecting cord

Strip 

wires

Green + 

Yellow

20mm

Strip 

wires

Connecting cord

Green + Yellow 

(ground)

Indoor Unit

Outdoor Unit

Connecting 

cord

Cord band

After remove the screw
and terminal cover, and
put the connecting cords
and fix the terminal cover
with screw.

Earth

 WARNING

When the fuse (F5 or F6) has been blown out by the improper connection of 
power cable, it can be restored by the attached reserve fuse.
Please exchange the blown-out fuse after making sure the right connection.    

RAK_RAS_18/25/35/50PEB_25/35/50PEBC_IM_EN          1

Pull downward

Please face this side (suction side)
of the unit to the wall.

Please remove terminal cover
when connecting the piping
and connecting cord.

RAC-50WEB

 

BUSH

Push

Push

DRAIN HOLE

DRAIN HOLE

above
100mm

BASE

BUSH

Outer diameter:

16 mm or more

7  DRAIN PIPE

RAC-50WEB

6,35 (1/4")
9,52 (3/8")

0 - 0,5
0 - 0,5

1,0
1,0

0 - 0,5

1,0

12,7 (1/2")

Outer                           A (mm) Rigid Flaring Tool
Diameter (Ø)

For R410A tool

For R22 tool

6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
6.35 (1/4")
9.52 (3/8")

13.7-18.6 (140 - 190)
34.3-44.1 (350 - 450)
44.1-53.9 (450 - 550)
19.6-24.5 (200 - 250)
19.6-24.5 (200 - 250)

12.7 (1/2")

12.3-15.7 (125 - 160)

Small diameter side 

Outer diameter 

of pipe (ø)

Large diameter side 

Small diameter side 

Large diameter side 

Valve core cap

Torque N·m 

(kgf·cm)

Valve

head cap 

29.4-34.3 (300 - 350)

L N 1 2 3

RAC-50WEB

Abdeck

              

L N 1

 

2

 

3

  

 

 cover

Earth terminal

Cord band

Service switch (If the switch is pressed for one
or more seconds, the force-cooling operation
starts. If the switch is pressed for additional
one or more seconds, the operation stops.)

RAC-50WEB

RAC-50WEB

RAC-18/25/35WEB

A time delay fuse

25

Wire length

up to   6m

1.5mm

2

up to 15m

2.5mm

2

up to 20m

4.0mm

2

Wire cross-section

Screw

H-LINK RAC Adapter:CN7

How to connect the optional parts

(H-LINK 

RAC Adapter, Dry contact, Wired Remote Controller)

Dry contact: CN6

RAC-18/25/35WEB

RAC-18/25/35WEB

RAC-18/25/35WEB

RAC-18/25/35WEB

Отзывы: