CHECKING THE OUTDOOR UNIT ELECTRICAL PARTS
MODEL RAC-25CNH2
[No operation or abnormal operation]
Is 220-240 being supplied to
ter
minal A and B?
Is the 15A fuse normal?
Is the power circuit normal?
See the description on
power circuit for details.
Is the 5V being generated
between REG 1 fin (0V) and
CN18 (test pin) pin
5
(5V)?
Operate the outdoor unit
according to the instruction
"How to operate the outdoor
unit independently".
How did the self-diagnosis
lamp (LD301) light?
LD301 blinks 10 times:
Half v
oltage error
.
If the 15A fuse has blown, be aware
that other parts may alsobe defective
(mainly
, v
a
rister 2, diode stac
k,
smoothing capacitors, power module,
etc.).
Is the switching power circuit OK?
Has the 3A fuse blown?
See the self-diagnosis lamp
lighting mode.
Are the cords, etc. of terminal
board, reactor
, diodes
, smoothing
capacitors, etc. connected?
Replace any defective parts.
Check to see whether the
connected C and D cable
correctly? If reversed, correct the
cable connection.
Replace any defective parts.
If the 3A fuse has blown, the
tr
ansf
or
mer
, R216, etc.
ma
y
also be defective.
If they are loose or disconnected,
inser
t them securely
.
()
No
No
No
Ye
s
Ye
s
Ye
s
No
No
Ye
s