– 52 –
CAUTION
Remote control is disabled while the Timer lamp is fl ashing.
To check operation, turn off the power switch and turn it on again.
Timer-Lamp, break-down checking in blinking sign.
Check the break-down factor from the frequency of timer-lamp blinking.
No.
Mode of Timer-Lamp blinking
Indication Factor
Estimated Break-Down Part
Force cooling operation
Unit is under forcible operation
or under balancing after forcible
operation.
Check force cooling switch at
indoor electrical.
IC 401 Data read wrongly
In case that data read from IC401
is wrong.
IC401 data is not in order.
Heat exchanger thermistor
error
Heat exchanger thermistor open
or short-circuit detected.
(1) Thermistor
(2) Indoor - control circuit board.
Room thermistor error
Room thermistor error open or
short-circuit detected.
(1) Thermistor
(2) Indoor - control circuit board.
1
2
3
4
5
( – – 0.5 second on, 0.5 second off.)
– – –– 15 times
– – – 14 times
– – – 13 times
– – – – – – – 2 times
!
DC Fan motor - over current of
electricity
Indoor - DC Fan motor has over
current of electricity.
(1) Indoor - Fan is locked.
(2) Indoor - Fan motor damage.
(3) Indoor - control circuit board.
– – –– 10 times
Содержание RAC-18G5
Страница 29: ... 27 MODEL RAC 18G5 ...
Страница 33: ... 31 CIRCUIT DIAGRAM Remote Control ...
Страница 34: ... 33 PRINTED WIRING BOARD LOCATION DIAGRAM MODEL RAS 18G5 ...
Страница 35: ... 35 BLOCK DIAGRAM MODEL RAS 18G5 RAC 18G5 ...
Страница 39: ... 43 REFRIGERATING CYCLE DIAGRAM MODEL RAS 18G5 RAC 18G5 ...
Страница 51: ... 55 PARTS LIST AND DIAGRAM OUTDOOR UNIT MODEL RAC 18G5 ...
Страница 53: ...PM NO 0485E Made in Malaysia RAS 18G5 RAC 18G5 ...