4. Check the control P.W.B. (power circuit)
Is 35V or 20V being output
at pin
5
relative to 0V at
pin
3
of CN3?
Is 12V or 7V being output
at (+) relative to 0V at (-) of
C114?
Is ICP1 normal?
Normal if it is less than 1
.
Blown (open) if it is 1
or more.
Replace ICP1. Check if the air
deflector motor is shorted, and
IC111, Q111, C114, ZD121 are
defective.
If shorted / defective, ICP1 will be
open again.
Replace the terminal board.
Insert the connection cable
securely.
Replace IC121. Check if a short
occurs in the 5V line.
If the 5V line is shorted, ICP1 will
be open again.
Check to see if the connection cables are
disconnected or reversed.
If normal, check the outdoor unit P.W.B.
Has the terminal board
thermal fuse blown (open)?
Replace Q111 and IC111.
Is DC5V being generated?
Perform final operation check.
1: When the unit is not in operation, the voltage across the 35V line may drop to 20V.
2: When the unit is not in operation, the voltage across the 12 V line may drop to 7V.
Yes
Yes
(Normal)
Yes
(Open)
Yes
No
No
No
Yes
No
No
1
2
07K394_RAS-14EH2_061-082_E
2007.10.31, 16:46
72
Содержание RAC-14EH2
Страница 22: ...RAS 14EH2 CIRCUIT DIAGRAM 20 07K394_RAS 14EH2_020 021_A2_E 2007 10 31 17 19 20 ...
Страница 25: ... 23 button 25 26 26 27 28 26 RAS 14EH2 07K394_RAS 14EH2_023_A3_E 2007 10 31 16 45 23 ...
Страница 92: ... 90 07K394_RAS 14EH2_083 092_E 2007 11 12 09 12 90 ...
Страница 94: ... 92 07K394_RAS 14EH2_083 092_E 2007 11 12 09 12 92 ...
Страница 95: ...HITACHI AW NO 0029E RAS 14EH2 RAC 14EH2 07K394_RAS 14EH2_000cover_E 2007 10 31 17 14 3 ...