Hitachi RAC-112SQB Скачать руководство пользователя страница 2

 

2

1. Safety Precautions 

 

Before installation, carefully read the “Safety Precautions” for correct installation. 

[Signs and Meanings] 

Warning: Incorrect operation may cause severe injury. 

: Items that must be followed. Make sure that both units for 

models must be earthed. 

: Prohibition. 
: Attention: Items that must be followed by general users. 

Precautions for Installation

 

W

arn

ing 

 

 

Install the unit according to the instructions in the installation manual. Incomplete or incorrect installation or 
failure to follow these instructions may cause water leakage, electric shock, or fire. 

 

Install with the special tools and piping materials for R410A refrigerant and according to the instructions in the 
installation manual. As the pressure of R410A, an HFC refrigerant, is 1.4 times higher than the previous R22 
refrigerant, use of incorrect piping materials or incorrect installation may cause an explosion, which leads to 
water leakage, electric shock or fire. 

 

Do not install in a location where flammable gas may be produced or flow in. This may cause fire. 

 

Make sure to install the units in locations that can provide full support of the unit’s weight. Otherwise, the unit 
may fall and cause injury. 

 

Do not climb on the air-conditioner or put objects on it to prevent collapse or overturning, which may cause 
injury. 

 

Make sure that no refrigerant leaks. Although Hitachi uses non-flammable, non-toxic, and odorless safety 
refrigerant (HFC), when HFC leaks and comes in contact with sparks, toxic gas produces. Also, as HFC has a 
higher mass than air, it will cause oxygen insufficiency near the floor. 

 

This model uses the non-flammable refrigerant R410A and non-flammable refrigeration oil Ze-GLES RB74 (JX 
Nippon Oil & Energy Corporation). Filling other types of refrigerants, gases, oxygen, propane, alcohol, or 
refrigeration oil with the special filling machine for R410A and Ze-GLES RB74 may cause machine failure and 
even explosion or fire. Make sure to use qualified refrigerant and refrigeration oil only. 

 

The machine maintains a high pressure at all times. Do not heat the machine or any parts in any situation. This 
may cause machine failure and even explosion or fire. 

 

Make sure to remove all flammable objects on-site before a welding operation. Otherwise, this may cause fire. 
Also, always wear leather gloves before handling refrigerant to prevent frostbite of the hand or the body. 

 

Clean up refrigerant with non-flammable, non-toxic cleaning agents only. Use of flammable cleaning agents 
may cause explosion or fire. 

 

Ensure adequate ventilation when working in confined spaces to prevent oxygen insufficiency. When cleaning 
agents are exposed to sparks at a high temperature, toxic gases may be produced. 

 

Make sure to recover the cleaning agent after use. Do not freely dilute CFCs in the atmosphere. 

 

Precautions for Electrical Works

 

W

arn

ing 

 

 

Always ask a qualified electrician to carry out electrical work with reference to the national regulations and the 
instructions in this manual. Make sure to use an individual circuit for the air-conditioner. Failure to follow 
instructions in this manual, insufficient circuit capacity or improper construction may cause electric shock or 
fire. 

 

Connect units with wires of the correct types and gauges. Use of incorrect wires may cause electric shock or fire.

 

Wires should be securely locked on terminals. Loosened connection of wires will cause overheating of terminals 
and fire. 

 

When securing wires on a terminal, make sure wires are unaffected by external influence. Improper connection 
may cause overheating of wires and fire. 

 

Make sure to earth the indoor and outdoor units according to relevant electrical requirements. Unearthed indoor 
and outdoor units may cause electric shock. Do not earth indoor and outdoor units a gas pipe, water pipe, 
arrester, or phone line. Incomplete earth may cause electric shock. 

 

It is necessary to install an earth leakage circuit breaker (ELCB). The absence of an ELCB may cause electric 
shock or fire. 

 

Make sure to disconnect power supply before wiring and electrical inspections to prevent electric shock. 

 

Keep wires away from places where rats or other animals may bite the wires to prevent fire. 

 

When installing the panel cover, avoid jamming wires together to prevent electric shock and fire. 

 

Pay special attention to “

Warning” signs. Failure to follow these warning signs during installation (incorrect installation) 

may cause severe injury. They are thus extremely important and must be strictly followed. 

● While checking any abnormality during the test run after installation, explain to customer the correct methods of usage 

and   maintenance  according  to  the  instructions  of  user’s  manual.  Then  hand  over  the  installation  manual  and  user’s 
manual to customers. 

Содержание RAC-112SQB

Страница 1: ...or animals directly under the airflow as it is bad for them As light will affect signal receiving of the remote control keep the signal receiver at least one meter away from lights to ensure signal receiving of the wireless remote control Temperature Ranges of Use Condition Function Indoor Unit Air Temperature Outdoor Unit Air Temperature Air conditioning 5ºC DB to 43ºC DB 21ºC DB 15ºC WB to 32ºC ...

Страница 2: ...lso always wear leather gloves before handling refrigerant to prevent frostbite of the hand or the body Clean up refrigerant with non flammable non toxic cleaning agents only Use of flammable cleaning agents may cause explosion or fire Ensure adequate ventilation when working in confined spaces to prevent oxygen insufficiency When cleaning agents are exposed to sparks at a high temperature toxic g...

Страница 3: ...ench y 2mm larger than the Φ12 7 or Φ15 88 wrenches for use on R410A pipes Not suitable for use on the pipes of currently used refrigerants For locking cap nuts y Φ6 35 and Φ9 53 wrenches can also be used Welder y Weld pipes as instructed flame adjustment welding temperature and choice of welding materials For welding refrigerant pipes Nitrogen y Strictly prevent dust from entry Following the nitr...

Страница 4: ...7 0 8 O 0 8 O 0 8 O Φ15 88 1 0 O 1 0 O 1 0 O Φ19 05 1 0 O 1 0 O 1 0 1 2H Φ22 2 1 2 O 1 15 O 1 0 1 2H Φ25 4 1 2 O 1 0 1 2H 1 0 1 2H Φ28 6 1 4 O 1 0 1 2H 1 0 1 2H Φ31 75 1 4 O 1 1 1 2H 1 1 1 2H Φ38 1 1 65 O 1 15 1 2H 1 35 1 2H Connector Selection The wall thickness of connectors elbows and tubing must be changed according to the design pressure change As 1 2H parts cannot be bend or expanded select ...

Страница 5: ...PSW3 switches on the mainboard of outdoor unit for three seconds 2 3 Outdoor unit installation 1 Installation space Retain maintenance space for the outdoor unit as shown below unit mm Standalone Standalone Standalone Two or More Units side by side No obstruction above No obstruction on sides and above Obstruction in front of the air outlet Even both sides are clear of obstruction maintain at leas...

Страница 6: ... Do not install the unit at locations where strong wind may blow off the roof or wall Secure the unit with steel wire if necessary 2 Add rubber cushions to the four legs of the unit stand 3 The location should be convenient for draining rainwater and condensate from defrosting For good drainage the outdoor unit should be installed in places with draining facilities When installing under roofs wher...

Страница 7: ...on A when using this type of anchor bolts Otherwise it will be difficult to remove the pipe cover 5 Securely fix the outdoor unit on the foundation to prevent collapse in a strong wind or an earthquake or noise due to loss of level leaning aside 6 When using ordinary frames whose legs are narrower than the legs of the outdoor unit add a board under the legs of the outdoor unit as shown in the figu...

Страница 8: ... When the outdoor unit is higher than the indoor unit 30 30 When the outdoor unit is lower than the indoor unit 20 20 2 Refrigerant pipe size Indoor unit Outdoor unit Capacity Level Refrigerant Pipe Size mm Gas Side Liquid Side 112 125 140 160 Φ15 88 Φ6 35 Φ9 53 Refrigerant Pipe Size mm Gas Side Liquid Side Φ15 88 Φ9 53 The diagram shows one outdoor unit with four indoor units In this example only...

Страница 9: ...ceptor valve on the pipe union Ⓐ in the right diagram of the gas interceptor valve Follow the instructions below Operation Air Conditioner Pipe union Ⓐ on the gas interceptor valve Low pressure Pipe union Ⓑ on the liquid interceptor valve Filling refrigerant after evacuation or repair Note After removing the filling hose prevent refrigerant and refrigeration oil from contaminating the electrical p...

Страница 10: ...ing the unit put back the pipe cover afterwards Wrap pipes with insulation sheets prepare on site before penetrating pipes through the cap hole to ensure it is seamless Make sure that there is adequate space for putting back the pipe cover Panel removal direction Rear piping Pipe cover Front piping Right piping Bottom piping cover y As shown in the left diagram pipes can be installed in four locat...

Страница 11: ...wards 5 Make sure to check leakage with a leakage detector and bubbles Do not use bubble liquids containing NH3 Recommended bubble liquids for the leakage test tabulated below Do not use general household detergents in the bubble test 2 Refrigeration filling 1 The unit has been equipped with refrigerant before shipping If pipes are longer than the design range add suitable amount of refrigerant on...

Страница 12: ...below W additional refrigerant L l x P L Pipe length l Standard pipe length 30m P Compensational value 60g m Example L 34m L l 34 30 4m Additional quantity of refrigerant W L l x P 4m x 60 g m 240g 3 Fill in the additional quantity of refrigerant W calculated in 2 3 5 Recovering Refrigerant Follow the steps below to recover refrigerant from the outdoor unit before relocating the indoor and or outd...

Страница 13: ...VVS KPEV S are used for connecting the operation circuit of the indoor and outdoor units earth with shielded wires Precautions for H LINK system connection y The factory setting of unit terminal impedance DSW5 1 ON is shown on the right diagram When more than two outdoor units are connected to the H LINK disabled the terminal impedance DSW5 1 OFF from the second outdoor unit onward Make sure that ...

Страница 14: ... Selection Determine the rated current of the ELCB based on the total wiring capacity shown in the right table Determine the ELCB model sensed current and trip current based on the information shown in the right table Use high sensitivity high speed trip time 0 1 second ELCB Confirm the ELCB rated current sensitivity and trip time and protective coordination of the upper part Rated Current A ELCB ...

Страница 15: ...ing the electrical panel for wiring or service to prevent electric shock Warning When installing the panel cover avoid jamming wires together to prevent electric shock and fire L1 1 L2 2 N Upper Right Panel Cover Earth cable Main power cable Operation circuit cable Keep an appropriate distance among terminals Insulate terminals with plastic tapes or bushings Plastic tapes or bushings Note Do not u...

Страница 16: ...ubleshooting in p 19 Contact a service technician for help if the situation persists When the operation light blinks every 2 seconds repeatedly this means there is a signal transfer error between the indoor unit and the remote control wires are loosened or disconnected broken incorrect wiring etc y A giggle sound also comes out from the mechanical chamber of the outdoor unit after compressor start...

Страница 17: ...igerant temperature Fluid pipe temperature ºC Compressor out temperature ºC 8 Refrigerant pressure Delivery pressure MPaG Intake pressure MPaG 9 Voltage Rated voltage V Operating voltage L1 N V L1 L2 V Start voltage V 10 Compressor input power and current Power kW Current A 11 Refrigerant filling level Correct Incorrect 12 Remote control functions Correct Incorrect 13 Protective device functions C...

Страница 18: ... Settings of each input terminal should be different The value of settings greater than the default value is invalid Not in use Not in use Heating Mode Operation Signal Cooling Mode Alarm Signal Stop Request Compressor ON Signal Force Stop Defrost Signal Current Control 60 Current Control 70 Current Control 80 Current Control 100 Input Setup 1 CN1 Code 1 2 Input Setup 2 CN1 Code 2 3 Input Setup 3 ...

Страница 19: ...t capacity mismatch Indoor unit capacity is 100 130 higher than the outdoor unit capacity 35 Indoor unit number setup error Repeated number setting or the number is greater than the connected number of indoor units 38 Protection check circuit error outdoor unit Error of the outdoor unit protection check circuit 41 Cooling overload high pressure switch activated When the outdoor unit protection act...

Страница 20: ...66MP1382 RAC AG C ...

Отзывы: