- 33 -
Notes:
(1)
The sleep operation starts when the sleep button is pressed.
(2)
When the sleep button is set, the indoor fan is set to “sleep Lo”.
(3)
The indoor fan speed does not change even when the fan speed mode
is changed.
(4)
If sleep operation is canceled by the cancel button or sleep button, all
data is cleared.
+
+
–1.33˚C
–0.66˚C
Notes:
(1)
The operation is done assuming as
the
preset
temperature
= (room temperature at the time) – (2
˚C
).
(2)
The indoor fan is operated in the “Lo” mode. During thermo OFF indoor fan will be OFF for 5
(3)
When the operation is started by the themostat turning ON, the start of the indoor fan is
delayed 32 seconds after the start of compressor operation.
(4)
The compressor is operated forcedly for 3 minutes after operation is started.
(5)
The minimum ON time and OFF time of the compressor are 3 minutes.
minutes and ON for 1 minute.
Cooling Sleep Operation
One-More Timer
Cooling Defrost
Dehumidifying Operation
Start
Stop
Dehumidifying Sleep Operation
Sleep button
Operation lamp
Timer lamp
Remote control (Sleep)
Indoor fan
See basic
operation
Hi
Med
Lo
Silent
Sleep Lo
Outdoor fan
Horizontal
air deflector
Shut
Horizontal
Facing down
Compressor speed
Set to 7 hours
SDMAX or SDRPM
7hr
STARCP
Compressor speed
1hr
Room temperature
button
min.
min.
˚C
˚C
When time setting reservation is 1, 2 or 3 hours.
TEIOF
TEION
Cooling defrost signal
SFTMOR
Setting
Sleep button
Set to 2 hours
0.5hr
1hr
2hr
One-more timer inhibited
30min.
1 hour
3hr
Operation lamp
Remote control [Sleep]
Timer lamp
Indoor fan
Shut
Horizontal
Facing down
Hi
Med
Lo
Silent
Sleep Lo
Outdoor fan
See basic operation
Lo
SS
One-more timer monitoring
Max. 4 hours
Horizontal air
deflector
Compressor speed
Notes:
(1) When the sleep button is set, the maximum compressor speed is limited to CSZMAX and the indoor fan is set to “Sleep Lo” (F
CSOY).
(2) The indoor fan speed does not change even when the fan speed mode is changed.
(3) If operation mode is changed during sleep operation, all data including set temperature and time are cleared and the opera
tion newly
starts.
(4) When the operation is stopped while the sleep operation is being performed, the set temperature at the time the operation
is stopped
is retained and the time count will be continued.
(5) When the set time is changed while the sleep operation is being performed, all data including set temperature and time are
cleared
and the operation newly starts.
(6) If the sleep operation is cancelled by the cancel button or sleep button, all data are cleared.
(7) The indoor fan stops during sleep operation or when thermo is off.
(8) One-more timer operation is performed only once.
(9) There is no shift in the set temperature by elapse of time.
②
In case of continuous timer operation
Notes:
(1) After sleep operation reservation is made, the operation is stopped in 3 hours time and then one-more timer operation is r
epeated for
subsequent 4 hours.
(2) After one-more timer operation is stopped, the one-more timer operation is inhibited for 30 minutes.
Indoor fan
Hi
Med
Lo
Silent
Outdoor fan
Indoor heat exchanger temperature
2 min
30
sec.
See basic operation
See basic operation
Balance period
3min.
Compressor speed
Lo
15sec.
1min.
CMINHI
Reversing valve
(Cooling "on" model)
Reversing valve
(Cooling "on" model)