INSTALLATION MANUAL

7.  INITIALIZATION OF OPTIONAL SETTING AND INPUT/OUTPUT 

Normal mode (when unit is not operating)

The procedure for initialization of optional settings and input / output settings are as follows.

Press the “OK” switch and the “RESET” switch 
simultaneously for more than 3 seconds.

1. Change to the optional setting mode

2. Selection of Optional Setting Mode

“SERVICE” is indicated and the mode 
number is 

ß

 ashed.

Press the “TEMP.” 

E

” or “

F

” switch, 

select “07” for the 
optional input / output 
setting cancel mode, 
and then press the 
“OK” switch.

3. Selection of Indoor Unit

“07” 

ß

 ashes.

Select the address of the indoor unit to be 
returned to the optional setting-input/output 
factory settings.

Press the “TEMP.” control 

E

 or 

F

 switch 

and select the address of the indoor unit.

8

 

NOTES:

 

 

In case of control by using two remote controllers (Master and Slave), settings 
shall be operated by the master controller.  

 

 

In case of using old Indoor unit PCB, HLINK, This function is not availble, 
and it displayed “NO FUNCTION”.

 

 

If selecting the indoor unit address “AA”, the indoor units that do not have these 
initialization function cannot be restore to the factory setting.

4. Optional Setting and Input/Output Setting Initialization

Check to ensure there are no problems to reset 
the factory settings and perform this function.

Press “OK” switch and the 
initialization is performed.

It takes approximately 15 to 
30 seconds.

When displayed “CL”, the 
optional and input / output 
settings are initialized. 
(restore to factory settings.)

In case of performing to initialize the other indoor units, repeat the 
procedure from step 3.

In this case, the indoor unit address is completed to initialize, the 
indication “CL” is displayed.

Normal mode

In case that initialization is not required, press the “RESET” switch in step 4. 

Содержание PC-ART

Страница 1: ...d verstanden werden Das Handbuch für spätere Rückfragen aufbewahren Lire attentivement ce manuel avant taute utilization du climatiseur et le conserver pour référence ultérieure Leggere attentamente il presente manuale prima di utilizzare questo condizionatore d aria Conservarlo da parte per future consultazioni Leia e compreenda este manual antes de operar este ar condicionado Guarde este manual ...

Страница 2: ... setting switches T RUN test run indication Check check indication These tests appear when TEST RUN or CHECK are being performed 0ABNML alarm indicator 1SET TEMP set temperature indicator 2 1234S indicator setting schedule number 3Mon Tue Sun indicator day of the week indicator Indicates that central station or CSNet control is operating 4Swing louver indicator DEFROST indicator 5 SERVICE mode ind...

Страница 3: ... seconds wait 10 seconds and then press again The mode will change back to normal ATTENTION Setting the temperature Set the temperature by pressing the TEMP or switch The temperature increases 1 C when the switch is pressed max 30 C The temperature decreases 1 C when the switch is pressed min 19 C for COOL DRY and FAN modes min 17 C for HEAT mode The Þgure shows the temperature set to 28 C Setting...

Страница 4: ...e louver 1 For COOL and DRY modes the discharge air angle can be changed to 5 different positions For the heating operation it can be changed to 7 positions 2 To Þx the louver position Þrst press the SWING LOUVER switch to start the louver swinging and then press again when the louver reaches the required position 3 The discharge air angle is Þxed at 20 for the RCI series and 40 for the RCD series...

Страница 5: ...ther schedule number indicators go out and the ON time hour indicator for the number selected blinks SET 1 SCHEDULE ON 4 OFF 4 Press the SELECT FE DAY SCHEDULE switches to adjust the hour setting and then press again Hour is indicated and minutes blinks SET 1 SCHEDULE ON 4 OFF 5 Press the SELECT FE DAY SCHEDULE switches to adjust the minutes setting and then press again Minutes is indicated and th...

Страница 6: ...he timer is in cancellation mode hold down the FE DAY SCHEDULE switches for more than 3 seconds NEXT SCHEDULE is indicated Timer activation Mon 1234S NEXT SCHEDULE ON Setting the temperature shifts energy saving mode 1 Set the ON OFF operation as in steps 1 and 2 of the Setting the timer section and then select S as the schedule number 1234S SCHEDULE ON 4 OFF SET 2 Set the ON OFF operation in step...

Страница 7: ...dication OPER LOCK blinks Mon NEXT SCHEDULE OFF OPER LOCK Cancellation While the locking operation is activated hold down the switch and SELECT simultaneously for more than 3 seconds to return to normal mode The locking operation will be cancelled and the OPER LOCK indication goes out Mon NEXT SCHEDULE OFF 8 NOTE The switch to be locked can be selected from operation mode change temperature settin...

Страница 8: ...ddress function may be performing Cancel the Test Run mode and set it again unit Test Run Period min Example when 5 indoor units are connected 5 CHECKING PROCEDURE 4 1 8 INDICATIONS UNDER ABNORMAL CONDITIONS Disfunction The RUN indicator red blinks The ALARM indicator appears on the liquid crystal display The indoor unit number the alarm code and the model code are indicated on the liquid crystal ...

Страница 9: ...its 2 The address of indoor unit not connected is not indicated SERVICE is indicated and the mode number is ßashed Press the TEMP switch and set 01 to 07 Then press the OK switch 2 Selection of Optional Setting Mode Input Output Setting Mode Mode Number 02 4 Selection of Input Output Number Input Output Number Select the input output number by pressing the TIME E or F switch Example When selecting...

Страница 10: ...control by using two remote controllers Master and Slave settings shall be operated by the master controller In case of using old Indoor unit PCB HLINK This function is not availble and it displayed NO FUNCTION If selecting the indoor unit address AA the indoor units that do not have these initialization function cannot be restore to the factory setting 4 Optional Setting and Input Output Setting ...

Страница 11: ... by Total Heat Exchanger Bypass Ventilation No Total Heat Exchanging 00 01 02 Econofresh Not available All fresh mode 38 E2 Increasing Supply Air Volume 00 01 Not Available Available 39 E3 Not Prepared 00 01 Not Used Use as 00 conditions 40 E4 Precooling Preheating Period 00 01 02 KPI Standard 30 min 60 min 00 01 02 Econofresh Standard CO2 Sensor 41 E5 Not Prepared 00 01 Not Used Use as 00 conditi...

Страница 12: ...ialization Mode b Address Check Mode This function is for two or more the indoor units are connected to the remote control switch The indoor unit address can be checked by the indoor unit individual operation with selecting the indoor address Normal Mode when unit is not operating 05 Indicates Press the TEMP or switch and select the address of the indoor unit Select the address of the indoor unit ...

Страница 13: ... address range The result of changing the address is displayed several seconds after the OK switch has been pressed AH is temporarily displayed if address change processing has been completely succeeded while EE is temporarily displayed if the address was unable to be changed If this happens repeat the procedure for changing the address 4 Change the address of the indoor unit 5 Changing the addres...

Страница 14: ...igerant cycle number to be set change from ßashing to remaining lit Repeat the setting procedure from step 3 when initializing the addresses of other indoor units Press the RESET switch to end address initialization Press the TEMP or switch and select the address of the indoor unit Press the TEMP or switch select either 06 for the address initialization mode and then press the OK switch 1 Change t...

Отзывы: