8.  Elevating Grille Group Setting and Cancellation

Group setting of the elevating grille refers to a function that allows all settings for the elevating grille (setting of elevating 

functions for input 2 and outputs 1 and 2) to be made all at once for all indoor units connected to the controller.  Settings 

are made by following the procedure as follows.

NOTES:

*  In case of using by two controllers (Main and Sub), the settings shall be operated by the main controller.
*  Group settings are made to all indoor units connected to the controller regardless of whether or not these are actually provided with 

the elevating grille. The indoor unit to be set cannot be selected.  (In this case, refer to section 5, “Optional Setting and Input/Output 

Setting from Controller”.)

*  Please note that when functions other than the elevating grille have been set for input 2 and output 1 and 2, those settings are 

cleared (namely, there are overwritten by the elevating grille function).

1. Switch to the elevating grille group setting mode.

2. Elevating grille Group Setting Procedure

"GRL" is 

displayed.

Press the "RUN/STOP" switch when making group 

settings.  (Press the "RESET" switch to return to the 

normal mode without making group settings.)

"RESET" 

Switch

"RUN/STOP" 

Switch

3. Display Following Elevating Grille Group Setting Procedure

"SET" flashes 

for 3 seconds.

The elevating grille settings are made for all indoor units 

connected to the controller.  "SET" flashes for 3 seconds after

settings have been made, and then automatically returns to the

normal mode.

O L

O

C

HIGH

/ C

A

O L

O

C

HIGH

/ C

A

SET

Normal mode (when unit is not operating)

Press the “CHECK” switch and the ”RESET” 

switch simultaneously for more than 3 seconds.

2. Select the input/output setting mode.

"02" Indicates.

3. Select the unit to be set.

The address and refrigerant cycle 

number of the indoor unit to be 

set are displayed (the diagram at 

left shows the No. 1 cycle and the 

No. 2 indoor unit).  All units are 

displayed at once when "AA" is 

set for both the refrigerant cycle 

number and address.

Example: Display in case of 

group cancellation of all units.

4. Group cancellation procedure

Press the "

switch.

The elevating grille settings for the selected 

units are canceled all at once and input 

1 and output 1 and 2 are returned to the 

factory settings.  "NO FUNCTION" flashes 

for 2 seconds following this procedure.

"NO FUNCTION" flashes for 2 

seconds

Press the "RESET" switch to cancel the 

cancellation procedure.

Normal mode 

O L

O

C

HIGH

/ C

A

SERVICE

SET TEMP.

O L

O

C

HIGH

/ C

A

SERVICE

ADDS RN 

O L

O

C

HIGH

/ C

A

SERVICE

ADDS RN

O L

O

C

HIGH

/ C

A

SERVICE

ADDS RN 

NO FUNCTION

Press the "TEMP."   or   switch, 

select the address of the indoor 

unit to be set and then press the 

"CHECK" switch.

Press the "TEMP."   or   switch, 

select "02" for the input/output 

setting mode, and then press the 

"CHECK" switch.

When canceling elevating grille settings for 

other units, repeat selection of the indoor units 

by pressing the "TEMP."    or   switch.

Normal mode (when unit is not operating)

1. Change to the optional setting mode.

Press the “CHECK” switch and the “RESET” 

switch simultaneously for more than 3 seconds.

“SERVICE” is 

indicated and the 

mode number is 

flashed.

317B39060(Q), 2016 

© 2016 Johnson Controls-Hitachi Air Conditioning Technology (Hong Kong) Ltd.

Elevating grille settings can be cancelled all at once by following the procedures as follows.

● Elevating Grille Group Cancellation Procedure

● Elevating Grille Group Setting Procedure

Содержание PC-AR

Страница 1: ...g of flammable gas is detected 4 Where the sea is near in the salty environment 5 An acid or alkaline environment DO NOT install the indoor unit outdoor unit controller and cable within approximately 3 meters from strong electromagnetic wave radiators such as medical equipment In case that the controller is installed in a place where there is electromagnetic wave direct radiation shield the contro...

Страница 2: ...able through the conduit tube in the wall 3 Electrical Wiring JIS Box for 2 Controllers JIS Box for 1 Controller M4 Screws Field Supplied Remove the protection film A B Connect the terminals 2 4 Installation Procedures 1 Insert the edge of the slotted screwdriver into the groove at the bottom of the holding bracket push and turn the slotted screwdriver and then remove the controller from the holdi...

Страница 3: ...Refer to the Technical Catalog provided with each indoor unit when performing electrical wiring work between the controller and indoor units for setting the refrigerant cycle number and the indoor unit address E No gap shall exist between the remote control cable and hole of the controller case If there is a gap cover the gap with vinyl tape If not malfunction may occur due to entrance of water dr...

Страница 4: ...The address is indicated by 0 to 15 NOTES 1 In case that the both indications of the ADDS and RN show AA the same setting is performed to all the indoor units 2 The address of indoor unit not connected is not indicated SERVICE is indicated and the mode number is flashed Press the TEMP or switch and set 01 or 02 Then press the CHECK switch 2 Selection of Optional Setting Mode Input Output Setting M...

Страница 5: ...ndoor units repeat the procedure from step 3 In this case the indoor unit address is completed to initialize the indication CL is displayed Normal Mode V V V SERVICE is indicated and the mode number is flashed In case that initialization is not required press the RESET switch in step 4 Check to ensure that there are no problems to restore the factory settings and perform to initialize Optional Set...

Страница 6: ...ons 27 Cd Not Prepared 00 01 Not Used Use as 00 conditions 28 CE Not Prepared 00 01 Not Used Use as 00 conditions 29 CF Change of Louver Swing Angle 00 01 02 Standard 7 Steps Draft Prevention 5 Steps High Ceiling 5 Steps 3 30 d1 Not Prepared 00 01 Not Used Use as 00 conditions 31 d2 Not Prepared Fixed Not Used 32 d3 Power Supply ON OFF 2 00 01 Not Available Available 33 d4 Prevention for Cooling D...

Страница 7: ...0 5 hour OFF Timer by 1 5 hours 52 F2 Remote Control Main Sub Setting 00 01 Main Sub 53 F3 Automatic Reset of Setting Temperature 4 00 01 Not Available Available 54 F4 Automatic Reset Time 00 01 02 03 30 min Factory Setting 15 min 60 min 90 min 55 F5 Automatic Reset Temperature for Cooling 5 19 20 25 29 30 19o C 20o C 25o C Factory Setting 29o C 30o C 56 F6 Automatic Reset Temperature for Heating ...

Страница 8: ...mperature is changed and kept within the set time at F4 the temperature is automatically changed to F5 and F6 In case that the set temperature is out of range at F5 and F6 it is applied within upper and lower limit for the set temperature 5 Applicable to fan cooling and dry operation modes 6 Applicable to heating operation mode 7 Operation is stopped by pressing the RUN STOP switch for 3 seconds X...

Страница 9: ...or which the address is to be changed is able to be checked When selecting another indoor unit first stop the operation of the indoor unit currently being checked NOTES All operations other than operation of the RUN STOP switch are not available during the address checking Do not operate from the central station during the address checking Press the RESET switch during the indoor unit operation OF...

Страница 10: ...ing the address is displayed several seconds after the CHECK switch has been pressed AH is temporarily displayed if address change processing has been completely succeeded while EE is temporarily displayed if the address was unable to be changed If this happens repeat the procedure for changing the address 4 Change the address of the indoor unit 5 Changing the address of another indoor unit Select...

Страница 11: ...itialization function the address and refrigerant cycle number to be set change from flashing to remaining lit Repeat the setting procedure from step 3 when initializing the addresses of other indoor units Press the RESET switch to end address initialization Press the TEMP or switch and select the address of the indoor unit Press the TEMP or switch select either 06 for the address initialization m...

Страница 12: ...Press the CHECK switch and the RESET switch simultaneously for more than 3 seconds 2 Select the input output setting mode 02 Indicates 3 Select the unit to be set The address and refrigerant cycle number of the indoor unit to be set are displayed the diagram at left shows the No 1 cycle and the No 2 indoor unit All units are displayed at once when AA is set for both the refrigerant cycle number an...

Отзывы: