7 TROUBLESHOOTING
7-11
7.5.2 Structure of trace control table
A trace control table consists of eight words.
Main Sub
/940FF0 /9C0FF0
①
Execution/stop
/940FF2 /9C0FF2
Unused
/940FF4 /9C0FF4
②
Trace target
address
/940FF8 /9C0FF8
③
Mask data
/940FFA /9C0FFA
④
Comparison data
/940FFC /9C0FFC
⑤
Pointer
/940FFE /9C0FFE
Unused
Figure 7-4 Structure of Trace Control Table
①
Execution/stop
Used to set trace execution or stop.
0: Stop tracing
1: Continue tracing until the trace condition is met.
2: Continue tracing until the trace condition is met or until an error occurs.
When power is recovered or the resetting condition is cleared, a 2 is set. If an error is detected
or the trace condition is satisfied, tracing is stopped and a 0 is set.
②
Trace target address
Used to set the starting address of the condition trace target area.
③
Mask data
Set mask data for conditional tracing. Of the data bits, only the bit(s) set to 0 are masked off.
④
Comparison data
Set comparison data for conditional tracing. The comparison data is compared with the result
obtained by ANDing the trace target address in
②
and the mask data. If a match is found, the
condition holds.
⑤
Pointer
Used to point to the case in which the next trace data is to be stored. The newest trace data is
stored in pointer 1 (for 0, pointer 255).
Содержание LQE010
Страница 1: ......
Страница 2: ......
Страница 17: ...1 BEFORE USE ...
Страница 21: ...2 SPECIFICATIONS ...
Страница 23: ...3 NAMES AND FUNCTIONS OF EACH PART AND CABLING ...
Страница 27: ...4 USER GUIDE ...
Страница 39: ...5 OPERATION ...
Страница 46: ...6 MAINTENANCE ...
Страница 63: ...7 TROUBLESHOOTING ...
Страница 79: ...APPENDIX ...