5-2. Output Current Detection Characteristics
Frequency inverter has several detection characteristics for output current to protect IGBT from break
down, or to protect motor from over heat.
[1] Over current
Frequency inverter shuts off the output instantaneously when output current exceeds to 200% of its
rated current.
e.g. Over current protection level of L100-015NFE (7.1 Amps of rated current) is
7.1 [Arms] * 200% = 14.2 [Arms] = 20.1 [A peak]
[2] Over load (Electronic thermal protection)
Frequency inverter shuts off the output when integration value of output current and time exceeds
specific value.
This Electronic thermal level can be changed from 50% to 120%. (Initial setting is 100%.)
200%
150%
180s
120s
time
150%, 60s
E-Thermal Level = [100]
No over load trip with
115% load
60s
180%, 10s
% output current of the rated current of the frequency inverter
0
100%
200%
150%
180s
120s
time
150%, 60s
60s
180%, 10s
% output current of the rated current of the frequency inverter
0
100%
50%
E-Thermal Level = [50]
5-3