(10) Over voltage at source (E 15)
Phenomena:
High voltage at power source line. Frequency inverter cannot protect source
overvoltage. If it is too high, frequency inverter will be damaged.
Cause:
Source voltage is too high.
Remedy:
Check the source voltage continously.
Insert AC reactor at source lines.
Way to Reset:
A
(11) Over temperature (E 21)
Phenomena:
Temperature sensor which located close to IGBT inside ISPM shows a too high
temperature.
Cause:
Ventilator blocked. (for models which has ventilator.)
Remedy:
Check ventilator
Cause:
The frequency inverter does not get enough cooling air.
Remedy:
Check cabinet ventilation, air filters, and ventilation openings in the cabinet.
Way to Reset:
A
(12) PTC error (E 35)
Phenomena:
Resistance of motor thermistor is high. This error can occur when you select
“PTC” function.
Cause:
Too much load of the motor.
Remedy:
Reduce the load, use bigger motor.
Cause:
Motor thermistor is not connected while PTC function is selected.
Remedy:
Disable PTC function when it is not used.
Cause:
Characteristics of the motor thermistor is not suitable. Frequency inverter gives
PTC error when the resistance value becomes more than 3k ohm +-10%.
Remedy:
Use motor which has suitable thermistor for the inverter.
Or change thermistor characteristics of the thermistor by debug mode.
Way to Reset:
A
Explanation of the way to reset.
A :
Make close the terminals between RS and P24 (CM1 only for Japanese version) on the I/O board, or
press “STOP/RESET” key of the operator.
3-5
Содержание L100 Series
Страница 3: ...Revisions Revision history table No Revision contents Date of issue Manual No ⅰⅰ ...
Страница 40: ......
Страница 59: ......
Страница 60: ......
Страница 61: ......
Страница 62: ......
Страница 63: ......
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ...End of page ...