Operation
Offset (1)
Name
Description
Values
Read/Write
22
OPER_CONDITION
Unit operation condition
0: OFF
1: Thermo OFF
2: Thermo ON
3: Alarm
Read
23
(Not used)
(Not used)
(Not used)
(Not used)
24
AMBIENT TEMPERA-
TURE
Ambient temperature (2)
-63ºC ~ 63ºC
Read
25
RCS_TEM
Remote control switch temperature
(only when available in the unit) (2)
-63ºC ~ 63ºC
Read
26
RCS_CONFIG
Remote control switch configuration
b0: 0 Master/1Slave
b1: 0 wih RCS/1 Without RCS
Read/Write
27
RCS_GROUP
Remote control switch group
0: No group
1~255
Read/Write
28~30
(Not used)
(Not used)
(Not used)
(Not used)
31
REM_TEM
Remote sensor temperature (2)
-63ºC ~ 63ºC
Read
N O T E
• (1) Register address is calculated as: “N + (Address * 32) + Offset” where:
• N: Data table position is 2000, position 20000 is also available to maintain compatibility with old Modbus gateway.
• Address: Indoor unit address as configured by configuration software.
• (2) These numbers refer to signed 16-bit value using 2-complement format for negative values
• (3) Bit 0 (ON/OFF) and Bit 4 (Louver) selectable only when all centrals are actived.
• In order to full lock setting from RCS (Central shown in RCS) set this register to 31.
10
PMML0351A rev.1 - 10/2015
Содержание HC-A64MB
Страница 2: ......
Страница 18: ......
Страница 30: ......
Страница 42: ......
Страница 54: ......
Страница 66: ......
Страница 78: ......
Страница 90: ......
Страница 102: ......
Страница 114: ......
Страница 126: ......
Страница 127: ......
Страница 128: ...Printed in Spain 00000 Copyright 2015 HITACHI Air Conditioning Products Europe S A U All rights reserved ...