Operation
5.2 AVAILABLE DATA
Offset (1)
Name
Description
Values
Read/Write
0
EXIST
Exist
0: No exist
1: Exist
Read
1
SYSTEM_ADDRESS
System address
0~63
Read
2
UNIT_ADDRESS
Unit address
3
SET_ONOFF
On/Off setting order
0: Stop
1: Run
Read/Write
4
SET_MODE
Mode setting order
0: Cool
1: Dry
2: Fan
3: Heat
4: Auto
Read/Write
5
SET_FAN
Fan setting order
0: Low
1: Medium
2: High
3: High2
4: Auto
Read/Write
6
SET_TSET
Setting temperature
17ºC ~ 30ºC
Read/Write
7
SET_LOUVER
Louver setting
0 ~ 7 (7 is Auto)
Read/Write
8
SET_CENTRAL
Central setting (3)
Bit 0: On/Off (always can be stopped)
Bit 1: Mode
Bit 2: Setting Temp
Bit 3: Fan
Bit 4: Louver
Read/Write
9
READ_ONOFF
On/Off status
0: Off 1: On
Read
10
READ_MODE
Mode status
0: Cool
1: Dry
2: Fan
3: Heat
4: Auto
Read
11
READ_FAN
Fan status
0: Low
1: Medium
2: High
3: High2
4: Auto
Read
12
READ_TSET
Setting temperature status
17ºC ~ 30ºC
Read
13
READ_LOUVER
Louver status
0 ~ 7 (7 is Auto)
Read
14
(Not used)
(Not used)
(Not used)
(Not used)
15
TIN
Inlet temperature reading (2)
-63ºC ~ 63ºC
Read
16
TOUT
Outlet temperature reading (2)
-63ºC ~ 63ºC
Read
17
TGAS
Gas pipe temperature reading (2)
-63ºC ~ 63ºC
Read
18
TLIQUID
Liquid pipe temperature reading (2)
-63ºC ~ 63ºC
Read
19
ERROR_CODE
Alarm code
Alarm unit from 7-segment
Read
20
STOP_CAUSE
Compressor stop cause
(Read unit service manual)
Read
21
VALVE_OPEN
Indoor unit expansion valve opening
0~100
(Not used)
9
PMML0351A rev.1 - 10/2015
ENGLISH
Содержание HC-A64MB
Страница 2: ......
Страница 18: ......
Страница 30: ......
Страница 42: ......
Страница 54: ......
Страница 66: ......
Страница 78: ......
Страница 90: ......
Страница 102: ......
Страница 114: ......
Страница 126: ......
Страница 127: ......
Страница 128: ...Printed in Spain 00000 Copyright 2015 HITACHI Air Conditioning Products Europe S A U All rights reserved ...