TEST RUN
5
/
13
ENGLISH
Next, setting for the required unit numbers are described below.
System
No.
Setting Pin
No.5 to No.8
System
No.
Setting Pin
No.5 to No.8
System
No.
Setting Pin
No.5 to No.8
System
No.
Setting Pin
No.5 to No.8
1
ON
1 2 3 4 5 6 7 8
5
ON
1 2 3 4 5 6 7 8
9
ON
1 2 3 4 5 6 7 8
13
ON
1 2 3 4 5 6 7 8
5. Setting of 8 Pins Dip Switch (S202)
Setting of 8 Pins DipSwitch (S202) is determined depending of the PCB quantity for
each H-LINK line.
Setting procedure for the system number and the unit number are described in the
table below.
8 Pins Dip Switch Setup
(S202)
Description
ON
1 2 3 4 5 6 7 8
Set only 1 PCB among other PCBs in a single H-LINK.
ON
1 2 3 4 5 6 7 8
Set the rest of the PCB other than the above.
5.2.
Test Run
1. Check if all procedures for “Wiring Connection” and “Dip Switch Setup” are completed.
2. Turn ON the Power supply according to the following procedure.
Switch ON the packaged air conditioners.
And then, Switch ON the HARC-BX E.
3. Check the connection of HARC-BX E.
The 7-Segment display will change as described in the table below, after switching ON
HARC-BX E.Check the 7-Segment display.
Step
7-Segment Display
Status
1
-
Power OFF
2
End of system initialization
3
Under Checking of Package Air Conditioner, Remote
Control Switch Group Connection Q’ty
4
Normal Transmission Between HARC-BX E, and Package
Air Conditioner are undertaking.