15
F ig. 14 E xam ple of closin g t im e
(2) Differen ce bet ween AC a nd DC oper at ions
Th e closin g t ime of AC oper a t ed cont a ctor a n d t h e double coil t ype DC oper at ed one is sh or t , a n d t h a t of t h e dir ect
in pu t t ype DC oper at ed on e is lon g. Th is is beca use t h e form er flow a la r ge cu r r en t a t closin g an d perform a t t r act ion
wit h a st r on g for ce, a n d a ft er closin g, t h e la r ge cu r r en t is ch a n ged t o a sm a ll cu r r en t . Th e r elea sin g t im e of DC
oper at ed con t act or is lon ger t h a n t h at of AC oper a t ed on e.
2-3-3 Su ppr ession of Coil Sur ge Volt a ge
Gen er a lly, in t h e sem i-con duct or cir cu it s, a n ext er n a l n oise gen er a t ed n ea r t hem m a y ca u se a n u n expect ed m a lfun c-
t ion . Wh en oper a t in g t h e con t a ct or , especia lly wh en cu t t in g off t h e excit in g cu r r en t of coil, t h e coil gen er a t es a
sh a r p su r ge volt a ge wit h t h e r esu lt t ha t t h e pea k volt a ge m a y r each high er t h a n 4k V a nd t h e frequ ency, h igh er t ha n
5kH z. Th is is r a diat ed as n oise t o t h e ou t side, a nd it is difficu lt t o preven t su ch n oise even if a pr ot ect ive elem en t is
pla ced in t he sem icondu ctor cir cu it . Ther efore, it is n ecessar y t o t a ke m ea sur es a ga inst occu r r en ce of noise from t he
coil. Con n ect coil sur ge a bsor ber in cludin g con denser a nd r esist or in ser ies t o t h e coil of t h e cont a ct or in par a llel.
Th en , t h e n oise gen er at ed fr om t h e coil when cut t in g off t h e excit in g cu r ren t ca n be r edu ced Coil su r ge a bsor ber is
sh own on ca ta logu e pa ge 42 a nd 43.