4.3.
SUSPENSION BOLTS
-
Select final location and installation direction of the indoor unit paying careful attention to the
space for the piping, wiring and maintenance.
-
Mount suspension bolts, as shown below:
- For Concrete Slab:
No
Description
o
Steel
p
Insert (100 to 150kg)
q
Concrete
r
Anchor Bolt (W3/8 or M10)
- For Steel Beam:
No
Description
o
I Beam
p
Suspension Bolt
(W3/8 or M10)
- For Wooden Beam Suspension:
No
Description
o
Wooden Bar
(60~90mm Square)
p
Wooden Beam
q
Square Washers
r
Nuts
s
Suspension Bolts
(W3/8 or M10)
4.4.
INSTALLATION
4.4.1.
Marking Position of the Suspension Bolts and Piping Connections
-
Mark position of the Suspension bolts, refrigerant piping connections and drain connection.
-