see if it is normal. 

b, higher temperature of compressor 

surface. 

C, cut off the discharging tube, to see if you 

can block the gas coming out of the tube 

when compressor is working. 

5) There is something 

that blocked the liquid 

cycle system 

Some time there is something blocked the 

filter of liquid cycle system, so that unit is not 

cold. 

Phenomenon of failure: 

a, lower pressure of discharging 

b, lower temperature of discharging. 

Change a new filter 

2.NO COOL 

(Popular failure reasons are below): 

Reason 

analysis 

Solutions: 

1) Leakage of gas 

Phenomenon of failure: 

a, leaking fast 

b, leaking slowly 

c, no voice of liquid flowing 

d, cut off charging tube, no gas 

goes out. 

First find out the point of leaking on tube, 

and then sealed it, vacuuming it, finally 

recharge with gas.   

Note

 

If you find oil on somewhere, it is possible 

that leakage point is there.   

2)There is some thing 

that blocked the liquid 

cycle system 

A, Ice blocking 

Sometime because unknown 

reason water comes into liquid 

cycle system, the capillary will be 

blocked by water after unit runs for 

period of time. 

Phenomenon of failure: 

The unit works well in the 

inception, after period of time the 

ice appears in the capillary and 

becomes more and more, till 

blocks the hole of capillary 

completely. In the moment you 

can find the ice on the evaporator 

defrosts. The noise of liquid flow 

disappears. The pressure of 

absorbing becomes negative.     

The phenomenon above will 

appear again and again. 

The way to check ice blocking: 

Warm the capillary with a hot 

towel, after a while the ice in the 

capillary melt, you can hear a 

sound of gas flow comes from the 

capillary abruptly. The pressure of 

absorbing becomes higher. It is 

Ice blocking. 

First stop unit for several minutes, and then 

open charging tube, discharge all of gas. 

Blow the cycle system with gas of nitrogen, 

and then recharge Gas, finally sealed the 

system.   

Содержание RS-09DC4S Series

Страница 1: ...REFRIGERATOR Service manual MODEL RS 09DC4S BD 65 NOTE This is a basic model the shape and specification of refrigerator is subject to change ...

Страница 2: ...PARTS INENTIFICATION NOTE This figure is only a sketch Of the Refrigerator and the actual Products may differ from it CIRCUIT DIAGRAM COOLING DIAGRAM ...

Страница 3: ...e guide for Disassembly Common parts of Refrigerator The instruction of replacing thermostat The location of the thermostat remove screws of top cover Capillary Compressor Dry filter Condenser Evaporator ...

Страница 4: ...ire Take out the thermostat The instruction of replacing PTC Starting relay and Overload protector Take down Spring tap and Cover Unplug the connecting wire Take out the PTC Starting relay and Overload protector Door Reversal ...

Страница 5: ...TROUBLESHOOTING The common problem judging method ...

Страница 6: ...opriate 4 2 Is there multi moisture food and too close to the back wall of the refrigerator 4 3 Is the ambient temperature too low 4 4 Is the electric parts on good condition specially the thermostat wich will cause the unit non stopping Abnormal noise 5 1 Is the refrigerator stably placed 5 2 Does the refrigerator bump other objects 5 3 Whether the internal accessory of the refrigerator is in the...

Страница 7: ...nit will work not well Phenomenon of failure a higher pressure of liquid cycle system than norm b higher temperature of condenser c larger electric current of compressor d there maybe ice on the suction tube e when gas is too much some gas liquid might goes back into compressor compressor will be damaged by liquid First stop unit for several minutes and then open charging tube discharge all of gas...

Страница 8: ...int is there 2 There is some thing that blocked the liquid cycle system A Ice blocking Sometime because unknown reason water comes into liquid cycle system the capillary will be blocked by water after unit runs for period of time Phenomenon of failure The unit works well in the inception after period of time the ice appears in the capillary and becomes more and more till blocks the hole of capilla...

Страница 9: ... Please put the food properly 5 Wind door is broken Replace wind door 6 Fan motor is broken Replace fan motor Note Before doing these operations above disconnect the main power supply Failure to do so could result in electrical shock or personal injury In case of any detailed technical information please check with the technical specifications announcements of Maintenance operation safety In order...

Страница 10: ...oper maintenance tools Improper use tools may cause bad contact or fastening rickety and accidents 6 Wire connection Reconnecting first must weld or use connected terminals and insulation tape sealing ensure good contacts 7 Insulation testing after the maintenance assembly the insulation resistance testing must use a multimeter to confirm insulation resistance up to 1 M Ω above can electrify opera...