3.5 Electrical wiring 

1

1

1

1

1

1

1

2

2

2

2

2

2

2

Power adapter

to AC100

-2

40V

Indoor unit

Outdoor unit

H-NET commu. cable

(non-polarity)

Electric 

meter

485 commu. 

cable

(polarity)

LAN port

HCCS-H64H2C1M

Router

Internet cable

(direct connection)

ON

OFF 1 2 3 4

Address DIP switch

H-NET commu

n

ication cable

 connects to H-NET terminal 

 and 

 of indoor unit and outdoor unit .

485 communication cable

 connects to the RS485 end of electric meter

.

 A connects to D1+, and B

connects to D0-. 

Internet cable

 connects to LAN port of router (when ad

o

pted wired connection).

Power adapter

 connects to the plug of AC100

-

240V. Select a proper AC plug according to actual on-

site conditions.

B   A

RS485

GND +12V

1   2

H-NET POWER

a. remove rubber plug and screws.

b. take off the case 

in

 the direction of the arrow.

1) Remove the case:

2

)

Connect electric wires according to the diagram below.

6mm

a. length of wire stripping.

b.

fix wire at the designated location of the trunking

.

Wiring Requirements

5

unit

mm

Содержание HCCS-H64H2C1M

Страница 1: ...Hi Mit Adapter Model HCCS H64H2C1M EN INSTALLATION USER MANUAL...

Страница 2: ......

Страница 3: ...2 1 Main features 2 2 Description of parts 2 3 General data 3 1 Components list 3 2 On site preparations 3 3 On site confirmation 3 4 Installation procedure 3 5 Electrical wiring CONTENTS 1 2 3 3 4 4...

Страница 4: ...of electric shock The adapter is non washable Otherwise it may lead to electric shock or a fire The power line and signal wire have to be kept away from wireless transmitter Please read this chapter t...

Страница 5: ...s both wired and wireless routers Only one type should be selected for use 4 Remote control air conditioner on ON OFF Temperature Mode Fan Louver settings etc 5 Remote control water module on ON OFF T...

Страница 6: ...nds Meanwhile the system status LED flashes The whole system is restored to factory settings connect to power adapter in accessories connect to commu bus of outdoor indoor unit Top cover Bottom cover...

Страница 7: ...connecting to internet with cable commu distance 50m Check the installation location and power supply Check if all the embedded lines are ready Check if the air conditioner can run properly Check if W...

Страница 8: ...able connects to the RS485 end of electric meter A connects to D1 and B connects to D0 Internet cable connects to LAN port of router when adopted wired connection Power adapter connects to the plug of...

Страница 9: ...meter has to be set Communication parameter adopts default parameter of the electric meter Baud rate 19200 parity even Slave address corresponding refrigerant system number 1 setting diagram is as sho...

Страница 10: ...e Text der EU Konformit tserkl rung ist unter der folgenden Internetadresse verf gbar http www hisense vrf com Qingdao Hisense Hitachi Air conditioning Systems Co Ltd No 218 Qianwangang Road Economic...

Страница 11: ...is connected Consult the dealer or an experienced radio TV technician for help To satisfy RF exposure requirements a separation distance of 20 cm or more should be maintained between the antenna of t...

Страница 12: ...ianwangang Road Economic and Technological Development Zone Qingdao China http www hisense vrf com E mail export hisensehitachi com The Company is committed to continuous product improvement We reserv...

Отзывы: