-25 48.488 25 5.0000 75 0.9217 125 0.2393 
-24 45.985  26  4.8110  76  0.8947 126 0.2335 
-23 43.627 27 4.6302 77 0.8686 127 0.2278 
-22 41.403 28 4.4572 78 0.8434 128 0.2224 
-21 39.305 29 4.2916 79 0.8190 129 0.2170 
-20 37.326 30 4.1331 80 0.7954 130 0.2118 
-19 35.458 31 3.9813 81 0.7726 131 0.2068 
-18 33.695 32 3.8359 82 0.7506 132 0.2019 
-17 32.030 33 3.6966 83 0.7292 133 0.1971 
-16 30.458 34 3.5632 84 0.7086 134 0.1924 
-15 28.972 35 3.4532 85 0.6886 135 0.1879 
-14 27.567 36 3.3125 86 0.6693 136 0.1835 
-13 26.239 37 3.1949 87 0.6506 137 0.1792 
-12 24.984 38 3.0821 88 0.6325 138 0.1750 
-11 23.795 39 2.9738 89 0.6149 139 0.1710 
-10 22.671 40 2.8699 90 0.5979 140 0.1670 

-9 21.606 41 2.7702 91 0.5815 141 0.1631 
-8 20.598 42 2.6744 92 0.5656 142 0.1594 
-7 19.644 43 2.5825 93 0.5501 143 0.1557 
-6 18.739 44 2.4942 94 0.5352 144 0.1522 
-5 17.881 45 2.4093 95 0.5207 145 0.1487 
-4 17.068 46 2.3278 96 0.5066 146 0.1453 
-3 16.297 47 2.2495 97 0.4930 147 0.1420 
-2 15.565 48 2.2741 98 0.4798 148 0.1388 
-1 14.871 49 2.1017 99 0.4670 149 0.1357 

0  14.212  50  2.0321 100 0.4546 150 0.1326 
1  13.586  51  1.9651 101 0.4426   

 

2 12.991 52 1.9006 102 04309   

 

3  12.426  53  1.8385 103 0.4196   

 

4  11.888  54  1.7788 104 0.4086   

 

5  11.378  55  1.7213 105 0.3980   

 

6  10.893  56  1.6660 106 0.3876   

 

7  10.431  57  1.6127 107 0.3776   

 

8  9.9912  58  1.5613 108 0.3679   

 

9 9.5727 59 1.5119 109 0.3584   

 

10  9.1743  60  1.4642 110 0.3493   

 

11 8.7948 61 1.4182 111 0.3403   

 

12  8.4332  62  1.3639 112 0.3317   

 

13  8.0086  63  1.3312 113 0.3233   

 

14  7.7602  64  1.2900 114 0.3151   

 

15  7.4470  65  1.2503 115 0.3072   

 

16  7.1482  66  1.2120 116 0.2995   

 

17  6.8632  67  1.1750 117 0.2920   

 

18  6.5912  68  1.1393 118 0.2848   

 

Содержание 88FZBpC

Страница 1: ...KFR 72LW 88FZBpC Maintenance manual Hisense Kelon Air Conditionning Co Ltd...

Страница 2: ...ment 7 5 2 Cooling run mode 19 5 3 Heating run mode 10 5 4 Dehumidifying mode 11 5 5 Air blowing mode 11 5 6 Dual mode 12 ELECTRICAL DATA 13 6 1 Electric Wiring Diagrams 13 6 2 Refrigerant Flow Diagra...

Страница 3: ...Page 2 of 36 MODEL AND BRAND 1 1 Model KFR 60LW 88FZBpC 1 2 Marketing Trademark Hisense Trademarks 1 3 Short Selling Frequency And Energy Saving...

Страница 4: ...Page 3 of 36 OUTLINES 2 1 INDOOR 2 2 OUTDOOR 2 3 REMOTE...

Страница 5: ...Various models are complete and can realize various functions 3 1 2 Touch screen Through the touch screen can intelligently adjust various refrigeration heating and other functions as well as wind sp...

Страница 6: ...with the large area of condenser and evaporator So air conditioner could run stable and reliable and energy efficient 3 2 3 Structural features Indoor structural elements is a new design Panels The u...

Страница 7: ...ing frequency range Minimum Max Hz 25 105 Rated Heating Capacity Rated input power of low temperature heating kW 6 5 2 80 Rated Input Current Maximum Input Current A 11 4 20 0 Maximum Input Power kW 4...

Страница 8: ...lay CPU receiving the signal from the indoor control board 6 1 4 Key Operation 6 1 4 1 Switch Key ON or OFF 6 1 4 2 Mode Key Switching mode cycle 6 1 4 3 Speed Key Switching wind speed loop 6 1 4 4 Te...

Страница 9: ...uring the time of sleep mode the set temperature will change automatically The air conditioner will turn off and cancel the sleep function after the sleep function works for 8 hours 6 1 8 High efficie...

Страница 10: ...thods see the corresponding mode 6 1 15 4 If shut down when the left throttle or intermediate damper in positioning uninterruptible power shutdown the leaves should be restored to the shutdown positio...

Страница 11: ...en fixed and swept according to the remote The left right throttle is targeted to the minimum position in cold air prevention mode 6 3 1 2 The blades of the top throttle control The top throttle is fi...

Страница 12: ...ange from cooling to heating it needs an interval of 50 seconds for the 4 way valve to change over from being interrupted to being electrified 6 3 6 Auxiliary Heating The unit automatically starts Aux...

Страница 13: ...age 12 of 36 6 6 Dual mode 6 6 1 Comfort mode is separated cooling comfort mode and heating comfort mode 6 6 2 Energy saving mode is separated cooling energy saving mode and heating energy saving mode...

Страница 14: ...Page 13 of 36 ELECTRICAL DATA 7 1 Electric Wiring Diagrams 7 1 1 Indoor 7...

Страница 15: ...Page 14 of 36 7 1 2 Outdoor...

Страница 16: ...Page 15 of 36 7 2 Refrigerant Flow Diagram 7 3 System pressure diagram...

Страница 17: ...Page 16 of 36...

Страница 18: ...Page 17 of 36 7 4 Air conditioning Appearance Dimension Drawing 1 Indoor...

Страница 19: ...Page 18 of 36 2 Outdoor...

Страница 20: ...essor is interrupted the outdoor LEDs are used to indicate the troubles listed below Symbols for indicator light ON flashing OFF LED1 LED2 LED3 Troubles 1 Normal 2 Room temperature sensor short circui...

Страница 21: ...pressor Pre heating condition 3 Voltage transformer in trouble 31 Key AD value converted failure 4 Current transformer in trouble 33 Room temperature sensor in trouble 5 IPM module protection 34 Indoo...

Страница 22: ...Page 21 of 36 8 2 Parts List and Details 8 2 1 Outdoor 8 2 1 1 Parts 19 21 30 31 34 33 29 28 32 27 26 25 23 22 24 20 9 8 7 5 4 3 2 1 35 18 6 12 13 11 10 14 17 16 15...

Страница 23: ...04863 STOP VALVE 1 17 1332842 STOP VALVE 1 18 K33AB0008 NOISE DEFENING COVER 1 19 1204841 COMPRESSORS BOX 1 20 1339309 COMPRESSORS 1 21 1204988 COMPRESSORS RUBBER 3 22 RZA 2 5304 003 XX 1 CLIP ASSY 1...

Страница 24: ...Page 23 of 36 8 2 2 Indoor 8 2 2 1 Parts...

Страница 25: ...010 XX 0 15 1202481 Magnet Components 3 RZA 0 2265 001 01 0 16 1338557 display panel 1 17 8007085 Vertical Wind Plate 1 18 8007109 Vertical Wind Plate 1 19 8007423 Care Net 1 20 8007481 Foam pieces 1...

Страница 26: ...Clasp 7 Fixed scroll 56 8007384 Support Parts 1 Pipe Clamp 57 1308927 Cover 3 58 1335430 Support Parts 1 Electrical Line Plate Sponge 59 1333210 Fan Motor 1 60 1331818 Fan scroll Parts 1 Scroll Spong...

Страница 27: ...nce characteristics of the sensor Thermistor1326150 Inner 1205710 Inner Coil 1326145 Outer 1201121 Outer coil Standard Resistance Characteristics Temp Center Temp Center Temp Center Temp Center 30 63...

Страница 28: ...8 20 598 42 2 6744 92 0 5656 142 0 1594 7 19 644 43 2 5825 93 0 5501 143 0 1557 6 18 739 44 2 4942 94 0 5352 144 0 1522 5 17 881 45 2 4093 95 0 5207 145 0 1487 4 17 068 46 2 3278 96 0 5066 146 0 1453...

Страница 29: ...20 0 0977 11 323 11 21 0 1025 10 306 77 22 0 1074 9 291 4 23 0 1123 8 276 92 25 0 1221 7 263 29 26 0 127 6 250 44 27 0 1318 5 238 33 28 0 1367 4 226 91 30 0 1465 3 216 13 31 0 1514 2 205 95 33 0 1611...

Страница 30: ...4 45 386 133 0 6494 35 43 703 138 0 6738 36 42 087 142 0 6934 37 40 536 147 0 7178 38 39 047 152 0 7422 39 37 616 157 0 7666 40 36 24 162 0 791 41 34 919 167 0 8154 42 33 648 172 0 8398 43 32 426 178...

Страница 31: ...78 8 9078 443 2 1631 79 8 577 453 2 2119 80 8 2577 462 2 2559 81 7 9495 472 2 3047 82 7 652 482 2 3535 83 7 3649 492 2 4023 84 7 0878 501 2 4463 85 6 8204 511 2 4951 86 6 5623 521 2 5439 87 6 3133 531...

Страница 32: ...08 2 7211 731 3 5693 109 2 6103 740 3 6133 110 2 5036 748 3 6523 111 2 4009 757 3 6963 112 2 3021 765 3 7354 113 2 207 773 3 7744 114 2 1155 781 3 8135 115 2 0276 789 3 8525 116 1 943 796 3 8867 117 1...

Страница 33: ...rol board fault and replace it no yes Normal protection action no Unexpected phenomenon yes Outdoor control board fault Fault self test code 4 Evaporation overload evaporator with high temperature yes...

Страница 34: ...n terminal block of outdoor unit Is there power output between 1 and 2 on terminal block of indoor unit Indoor Main Relay RY01 has output no no no no no Indoor control board fault and replace it yes C...

Страница 35: ...he fan fault and replace it yes Fault self test code11 Brightness sensor fault The cable between control board and display board is bad no Indoor control board fault and replace it Display board failu...

Страница 36: ...No Load Failure Compressor is running no Outdoor filter substrate failure and replace it IPM fault and replace it Is the voltage between P and N of the IPM normal no yes yes Is there voltage output b...

Страница 37: ...nutes and is compressor running no yes Check outdoor unit air and the installation of IPM and radiator working closely Then ensure that IPM radiator is cooling Is the IPM radiator hotter Fault self te...