Hisense 88FZBpC Скачать руководство пользователя страница 11

 

Page 10 of 36 

to the remote. 

6.2.2.2 Top outlet 

The top throttle is fixed at the maximum position. 

6.2.3 Outdoor Fan 

The speed of outdoor fan is single-speed. The outdoor fan is controlled on an off 

according to outdoor ambient temperature. 

6.2.4 

Prevention against condensation and insufficient heat exchange at the low 

indoor fan speed. 

When the indoor fan speed is set at the low fan speed, the compressor’s power is 

restricted as in the low temperature cooling. 

6.2.5 4-way valve 

State: 

It is interrupted in cooling.

 

Switchover: 

When initially electrified for cooling, the 4-way valve is interrupted 

immediately. 

When the heating is changed to the cooling, it needs an interval of 50 

seconds for the 4-way valve to change over from being electrified to being 

interrupted. 

 

6.3 Heating-run mode 

6.3.1 Throttle blade control 

6.3.1.1 The blades of the left-right throttle outlet 

The blades of the left-right throttle are switched between fixed and swept according 

to the remote. 

The left-right throttle is targeted to the minimum position in cold air prevention mode. 

6.3.1.2 The blades of the top throttle control 

The top throttle is fixed at the minimum position (the minimum position of 88 series 

Floor Type Air-Conditioner is 0, that is, is closed). 

The top throttle is fixed at the maximum position in cold air prevention mode. 

6.3.2 Indoor fan 

As cooling-run mode except for cold air prevention mode and defrosting mode (T= 

Tset-Tindoor ambient). 

6.3.3 Cold air prevention 

If the outlet wind temperature of the indoor is too low in heating, Users can feel the 

feeling of chilling by cold air. Cold air prevention function is that Controls the fan 

speed according to the indoor coil temperature, and regulates the air supply, thereby, 

Maintain indoor air supply at an appropriate temperature range, and improve the 

air-conditioned comfort. 

When the coil temperature reaches 20 

 after starting, indoor fan runs by the 

breeze. Then control indoor fan speed to increase progressively according to the 

indoor coil temperature. When the coil temperature reaches 38 

, the indoor fan 

Содержание 88FZBpC

Страница 1: ...KFR 72LW 88FZBpC Maintenance manual Hisense Kelon Air Conditionning Co Ltd...

Страница 2: ...ment 7 5 2 Cooling run mode 19 5 3 Heating run mode 10 5 4 Dehumidifying mode 11 5 5 Air blowing mode 11 5 6 Dual mode 12 ELECTRICAL DATA 13 6 1 Electric Wiring Diagrams 13 6 2 Refrigerant Flow Diagra...

Страница 3: ...Page 2 of 36 MODEL AND BRAND 1 1 Model KFR 60LW 88FZBpC 1 2 Marketing Trademark Hisense Trademarks 1 3 Short Selling Frequency And Energy Saving...

Страница 4: ...Page 3 of 36 OUTLINES 2 1 INDOOR 2 2 OUTDOOR 2 3 REMOTE...

Страница 5: ...Various models are complete and can realize various functions 3 1 2 Touch screen Through the touch screen can intelligently adjust various refrigeration heating and other functions as well as wind sp...

Страница 6: ...with the large area of condenser and evaporator So air conditioner could run stable and reliable and energy efficient 3 2 3 Structural features Indoor structural elements is a new design Panels The u...

Страница 7: ...ing frequency range Minimum Max Hz 25 105 Rated Heating Capacity Rated input power of low temperature heating kW 6 5 2 80 Rated Input Current Maximum Input Current A 11 4 20 0 Maximum Input Power kW 4...

Страница 8: ...lay CPU receiving the signal from the indoor control board 6 1 4 Key Operation 6 1 4 1 Switch Key ON or OFF 6 1 4 2 Mode Key Switching mode cycle 6 1 4 3 Speed Key Switching wind speed loop 6 1 4 4 Te...

Страница 9: ...uring the time of sleep mode the set temperature will change automatically The air conditioner will turn off and cancel the sleep function after the sleep function works for 8 hours 6 1 8 High efficie...

Страница 10: ...thods see the corresponding mode 6 1 15 4 If shut down when the left throttle or intermediate damper in positioning uninterruptible power shutdown the leaves should be restored to the shutdown positio...

Страница 11: ...en fixed and swept according to the remote The left right throttle is targeted to the minimum position in cold air prevention mode 6 3 1 2 The blades of the top throttle control The top throttle is fi...

Страница 12: ...ange from cooling to heating it needs an interval of 50 seconds for the 4 way valve to change over from being interrupted to being electrified 6 3 6 Auxiliary Heating The unit automatically starts Aux...

Страница 13: ...age 12 of 36 6 6 Dual mode 6 6 1 Comfort mode is separated cooling comfort mode and heating comfort mode 6 6 2 Energy saving mode is separated cooling energy saving mode and heating energy saving mode...

Страница 14: ...Page 13 of 36 ELECTRICAL DATA 7 1 Electric Wiring Diagrams 7 1 1 Indoor 7...

Страница 15: ...Page 14 of 36 7 1 2 Outdoor...

Страница 16: ...Page 15 of 36 7 2 Refrigerant Flow Diagram 7 3 System pressure diagram...

Страница 17: ...Page 16 of 36...

Страница 18: ...Page 17 of 36 7 4 Air conditioning Appearance Dimension Drawing 1 Indoor...

Страница 19: ...Page 18 of 36 2 Outdoor...

Страница 20: ...essor is interrupted the outdoor LEDs are used to indicate the troubles listed below Symbols for indicator light ON flashing OFF LED1 LED2 LED3 Troubles 1 Normal 2 Room temperature sensor short circui...

Страница 21: ...pressor Pre heating condition 3 Voltage transformer in trouble 31 Key AD value converted failure 4 Current transformer in trouble 33 Room temperature sensor in trouble 5 IPM module protection 34 Indoo...

Страница 22: ...Page 21 of 36 8 2 Parts List and Details 8 2 1 Outdoor 8 2 1 1 Parts 19 21 30 31 34 33 29 28 32 27 26 25 23 22 24 20 9 8 7 5 4 3 2 1 35 18 6 12 13 11 10 14 17 16 15...

Страница 23: ...04863 STOP VALVE 1 17 1332842 STOP VALVE 1 18 K33AB0008 NOISE DEFENING COVER 1 19 1204841 COMPRESSORS BOX 1 20 1339309 COMPRESSORS 1 21 1204988 COMPRESSORS RUBBER 3 22 RZA 2 5304 003 XX 1 CLIP ASSY 1...

Страница 24: ...Page 23 of 36 8 2 2 Indoor 8 2 2 1 Parts...

Страница 25: ...010 XX 0 15 1202481 Magnet Components 3 RZA 0 2265 001 01 0 16 1338557 display panel 1 17 8007085 Vertical Wind Plate 1 18 8007109 Vertical Wind Plate 1 19 8007423 Care Net 1 20 8007481 Foam pieces 1...

Страница 26: ...Clasp 7 Fixed scroll 56 8007384 Support Parts 1 Pipe Clamp 57 1308927 Cover 3 58 1335430 Support Parts 1 Electrical Line Plate Sponge 59 1333210 Fan Motor 1 60 1331818 Fan scroll Parts 1 Scroll Spong...

Страница 27: ...nce characteristics of the sensor Thermistor1326150 Inner 1205710 Inner Coil 1326145 Outer 1201121 Outer coil Standard Resistance Characteristics Temp Center Temp Center Temp Center Temp Center 30 63...

Страница 28: ...8 20 598 42 2 6744 92 0 5656 142 0 1594 7 19 644 43 2 5825 93 0 5501 143 0 1557 6 18 739 44 2 4942 94 0 5352 144 0 1522 5 17 881 45 2 4093 95 0 5207 145 0 1487 4 17 068 46 2 3278 96 0 5066 146 0 1453...

Страница 29: ...20 0 0977 11 323 11 21 0 1025 10 306 77 22 0 1074 9 291 4 23 0 1123 8 276 92 25 0 1221 7 263 29 26 0 127 6 250 44 27 0 1318 5 238 33 28 0 1367 4 226 91 30 0 1465 3 216 13 31 0 1514 2 205 95 33 0 1611...

Страница 30: ...4 45 386 133 0 6494 35 43 703 138 0 6738 36 42 087 142 0 6934 37 40 536 147 0 7178 38 39 047 152 0 7422 39 37 616 157 0 7666 40 36 24 162 0 791 41 34 919 167 0 8154 42 33 648 172 0 8398 43 32 426 178...

Страница 31: ...78 8 9078 443 2 1631 79 8 577 453 2 2119 80 8 2577 462 2 2559 81 7 9495 472 2 3047 82 7 652 482 2 3535 83 7 3649 492 2 4023 84 7 0878 501 2 4463 85 6 8204 511 2 4951 86 6 5623 521 2 5439 87 6 3133 531...

Страница 32: ...08 2 7211 731 3 5693 109 2 6103 740 3 6133 110 2 5036 748 3 6523 111 2 4009 757 3 6963 112 2 3021 765 3 7354 113 2 207 773 3 7744 114 2 1155 781 3 8135 115 2 0276 789 3 8525 116 1 943 796 3 8867 117 1...

Страница 33: ...rol board fault and replace it no yes Normal protection action no Unexpected phenomenon yes Outdoor control board fault Fault self test code 4 Evaporation overload evaporator with high temperature yes...

Страница 34: ...n terminal block of outdoor unit Is there power output between 1 and 2 on terminal block of indoor unit Indoor Main Relay RY01 has output no no no no no Indoor control board fault and replace it yes C...

Страница 35: ...he fan fault and replace it yes Fault self test code11 Brightness sensor fault The cable between control board and display board is bad no Indoor control board fault and replace it Display board failu...

Страница 36: ...No Load Failure Compressor is running no Outdoor filter substrate failure and replace it IPM fault and replace it Is the voltage between P and N of the IPM normal no yes yes Is there voltage output b...

Страница 37: ...nutes and is compressor running no yes Check outdoor unit air and the installation of IPM and radiator working closely Then ensure that IPM radiator is cooling Is the IPM radiator hotter Fault self te...

Отзывы: