![HISEER GSWW60 Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/hiseer/gsww60/gsww60_installation-operation-and-maintenance-manual_2138248023.webp)
22
Adjusting Parameter Values
Display
Procedures
After inputting password and enter into the parameter setting mode.
Press <Plus> or <Minus> to select the
parameter code, and press <Enter> to
confirm.
The default value of the parameter will
start flashing, allowing you to make a
change.
Press <Plus> or <Minus> to increase or
decrease the value, and press <Enter> to
confirm.
Continuously press <Esc> to exit out of the current level and back to the desired menu level.
User Settings
Para-
Meter
Descriptions
De-
fault
Min.
Max.
Unit Res
Priv-
ilege
ST01
Setting temperature at cooling mode (End User)
12
ST11
ST12
ºC
0.1
0
ST02
Setting temperature at heating mode (End User)
40
ST13
ST14
ºC
0.1
0
ST03
Setting temperature difference at cooling mode
1
0
10
ºC
0.1
0
ST04
Setting temperature difference at Heating mode
1
0
10
ºC
0.1
0
ST05
Setting temperature at heating for compensation
function
20
0
30
ºC
0.1
0
ST06
Compensation factor for heating compensation function
6
0
30
-
0.1
0
ST07
Outdoor temperature to start the boiler or electric
heater
0
-10
20
ºC
0.1
0
ST08
Boiler or electric heater stop outdoor temperature
difference
5
1
20
ºC
0.1
0
ST09
Hot water temperature
50
ST15
ST16
ºC
0.1
0
ST10
Hot water temperature difference
3
1
10
ºC
0.1
0
Controller