11
Electrical Connection
Q13 Q14
Q34
Q24
Q44 Q54 Q64
Q23 Q74 Q84
Y1 G0 Y2
A+
B- GND
RJ45
G0 PE
D1
M
D3
D2
M
M
D4
D5
X1
GND
X3
X2
X4
X5
GND
GND
+5V
X6
+24V
RS485
!
C
G
SIEMENS
RWR470.10
Terminal Assigments
Terminal Assignments
G
Power supply AC/DC 24 V
Q13
Supply 1 (AC 24 V 1230 V)
G0
Power supply ground
Q14
Compressor 1
PE
Saftey ground
Q24
Compressor 2
Q34
Indoor water pump
X1
Inlet water temperature of indoor side
Q44
Outdoor water pump
X2
Outlet water temperature of indoor side
Q54
4-way valve
X3
Outdoor ambient temperature
Q64
Electric heater or boiler
X4
Hot water temperature
X5
Outlet water temperature of outdoor side
Q23
Supply 2 (AC 24 V 1230 V)
X6
Exhaust
gas
temperature/return
gas
temperature
Q74
Hot water pump or revert valve
GND
Common reference point for analog input
Q84
Alarm
+5 V
DC 5 V power output for active sensor
Y1
Analog output 2, 0...10 V
+24 V
DC 24 V power output for active sensor
GND
Common reference point
Y2
Analog output 2, 0...10 V
D1
Water flow switch
D2
Low pressure switch
A+
A+ connector for RS485
D3
high pressure switch
B-
B- connector for RS485
D4
Air conditioner switch
GND
Optional for RS485 communication
D5
Hot water switch
RJ45
Service interface for parameters
uploading and downloading
M
Common reference point for digital input
Warning:
Electrical connections and servicing must be carried out under the supervision of a qualified
electrician
.
Electrical installation and wiring must be carried out in accordance with Local
Standards
.
Electrical Connection
Содержание GSWW60
Страница 25: ...24 Three curves of different ST05 setting Controller...