Installation OZD Profi 12M ...
Release 01 07/2017
39
4.2
Mounting the device
4.2.1
Installing the device onto the DIN rail
Note:
The device is for mounting on a 35 mm DIN rail in accordance with DIN
EN 60715.
Requirements:
Install the device in a location where the climatic threshold values
specified in the technical data are adhered to.
See “Technical data” on page 57.
Ensure that there is sufficient room to connect the bus and power supply
cabling.
Connect the optical fiber line before mounting the repeater as this
simplifies the procedure.
Proceed as follows:
Slide the upper snap-in guide of the device into the DIN rail.
Press the device downwards onto the clip-in bar.
2
1