HIRED-HAND ICS-500 Скачать руководство пользователя страница 29

 

Integrated Control System 500

 

27 

 

Resistance 

(Kohms)

 

Temp 

(F)

 

Temp 

(C)

 

Resistance 

(Kohms)

 

Temp 

(F)

 

Temp 

(C)

 

19.065 

51.6 

10.9 

9.956 

77.2 

25.1 

18.884 

52.0 

11.1 

9.869 

77.5 

25.3 

18.616 

52.5 

11.4 

9.741 

78.1 

25.6 

18.352 

53.1 

11.7 

9.614 

78.6 

25.9 

18.179 

53.4 

11.9 

9.530 

79.0 

26.1 

17.503 

54.9 

12.7 

9.407 

79.5 

26.4 

17.339 

55.2 

12.9 

9.325 

79.9 

26.6 

17.095 

55.8 

13.2 

9.205 

80.4 

26.9 

16.856 

56.3 

13.5 

9.086 

81.0 

27.2 

16.698 

56.7 

13.7 

9.007 

81.3 

27.4 

16.465 

57.2 

14.0 

8.891 

81.9 

27.7 

16.312 

57.6 

14.2 

8.815 

82.2 

27.9 

16.085 

58.1 

14.5 

8.702 

82.8 

28.2 

15.935 

58.5 

14.7 

8.590 

83.3 

28.5 

15.714 

59.0 

15.0 

8.517 

83.7 

28.7 

15.568 

59.4 

15.2 

8.408 

84.0 

28.9 

15.353 

59.9 

15.5 

8.336 

84.6 

29.2 

15.211 

60.3 

15.7 

8.230 

85.1 

29.5 

15.001 

60.8 

16.0 

8.125 

85.6 

29.8 

14.863 

61.2 

16.2 

8.056 

86.0 

30.0 

14.658 

61.7 

16.5 

7.954 

86.5 

30.3 

14.457 

62.2 

16.8 

7.853 

87.1 

30.6 

14.325 

62.6 

17.0 

7.787 

87.4 

30.8 

14.128 

63.1 

17.3 

7.689 

88.0 

31.1 

13.999 

63.5 

17.5 

7.592 

88.5 

31.4 

13.808 

64.0 

17.8 

7.496 

89.1 

31.7 

13.682 

64.4 

18.0 

7.433 

89.4 

31.9 

13.496 

64.9 

18.3 

7.340 

90.0 

32.2 

13.373 

65.3 

18.5 

7.248 

90.5 

32.5 

13.192 

65.8 

18.8 

7.157 

91.0 

32.8 

13.073 

66.2 

19.0 

7.098 

91.4 

33.0 

12.896 

66.7 

19.3 

7.009 

91.9 

33.3 

12.779 

67.1 

19.5 

6.922 

92.5 

33.6 

12.607 

67.6 

19.8 

6.836 

93.0 

33.9 

12.493 

68.0 

20.0 

6.779 

93.4 

34.1 

12.325 

68.5 

20.3 

6.695 

93.9 

34.4 

12.215 

68.9 

20.5 

6.612 

94.5 

34.7 

12.051 

69.4 

20.8 

6.531 

95.0 

35.0 

11.943 

69.8 

21.0 

6.450 

95.5 

35.3 

11.783 

70.3 

21.3 

6.371 

96.1 

35.6 

11.678 

70.7 

21.5 

6.319 

96.4 

35.8 

11.522 

71.2 

21.8 

6.241 

97.0 

36.1 

11.420 

71.6 

22.0 

6.165 

97.5 

36.4 

11.268 

72.1 

22.3 

6.089 

98.1 

36.7 

11.168 

72.5 

22.5 

6.015 

98.6 

37.0 

11.020 

73.0 

22.8 

5.941 

99.1 

37.3 

10.874 

73.6 

23.1 

5.869 

99.7 

37.6 

10.778 

73.9 

23.3 

5.798 

100.2 

37.9 

10.636 

74.5 

23.6 

5.728 

100.8 

38.2 

10.542 

74.8 

23.8 

5.658 

101.3 

38.5 

10.404 

75.4 

24.1 

5.590 

101.8 

38.8 

10.312 

75.7 

24.3 

5.522 

102.4 

39.1 

10.177 

76.3 

24.6 

5.456 

102.9 

39.4 

10.088 

76.6 

24.8 

5.390 

103.4 

39.7 

Содержание ICS-500

Страница 1: ...4801 0102 REV 9 96 ICS ICS 500 Environmental Controller 500 Environmental Controller With Back up system and Contactor Panel Hired Hand Inc 1733 Co Rd 68 PO Box 99 Bremen AL 35033...

Страница 2: ...6 3 3 Controls _____________________________________________________________________17 7 Operation _________________________________________________________________________18 7 1 Curtain Operation __...

Страница 3: ...a life support heating and ventilation system where failure could result in loss or injury the user should provide adequate back up or accept the risk of such loss or injury Warning Wiring and connect...

Страница 4: ...tely 18 apart leaving the heads away from the wall 3 Hang ICS 500 over the two screws The top two holes in the side flanges are slotted to allow easy hanging 4 Finish mounting the unit by securing the...

Страница 5: ...oller which uses knobs for user controls The controller can operate the following One curtain machine intelligently based on time Eight stages of heat and cool User selected 5 or 10 minute timer Any s...

Страница 6: ...ose Off The open close off switch is used for manual control of the curtains This switch is only operable when the automatic manual switch is in the manual position At other times this switch is not o...

Страница 7: ...re This setting is very important because all system operations other than the timer are operated by the distance between target temperature and actual temperature At all times the system will try to...

Страница 8: ...ages Stages Prog Bank A B C D E F 0 1 23456 7 8 9 A B C D E F 0 1 23456 7 8 9 To change stage programming use a small screwdriver to select one of the sixteen positions on the stages switch Each lette...

Страница 9: ...a negative timer 6 1 2 2 2 2 Stir Timers A stage on a stir timer may operate at any time regardless of curtain position To place a stage on stir timer push a two pin jumper on pins A B next to the sta...

Страница 10: ...Adjust This setting tells the controller how long to run the curtain machine when a change is needed If 60 seconds is selected the controller will run the machine for 60 seconds or until the curtain...

Страница 11: ...ersion of the controller these switches are not installed 6 1 2 2 7 2 Variable Span Adjust This setting controls the temperature difference between the minimum speed temperature setpoint and the maxim...

Страница 12: ...rget Temp 75 degrees The variable speed fan will run at 40 when the inside temp is 70 degrees target offset The controller will increase fan speed if inside temperature is rising up until 80 degrees t...

Страница 13: ...Integrated Control System 500 11...

Страница 14: ...Integrated Control System 500 12...

Страница 15: ...Integrated Control System 500 13...

Страница 16: ...ould exceed the limits set by the controller the back up system would engage the appropriate equipment For example If the temperature is below the low limit setpoint the back up board would engage all...

Страница 17: ...ton The last control on the back up board is the reminder reset button During a growout you lower house temperature as your animals mature It is vitally important to reset your high and low limits as...

Страница 18: ...Integrated Control System 500 16...

Страница 19: ...be in the right position according to the equipment on that particular stage If you have fans on a stage that stage s switch should be in the cool position The position of the switch determines whethe...

Страница 20: ...e activated except for stage 8 which depending on the program could be a fogger You will be alerted to this condition by the continual flashing of the TARGET and OSC HIGH LIMIT lights The machine will...

Страница 21: ...he controller uses an offset differential method for determining if a stage should be turned on or off This method is explained below Offset The point above cool or below heat target temperature where...

Страница 22: ...you know that the buzzer is working The buzzer has a five day timer that will continuously sound the buzzer after approximately five days Any time you press the button you reset the five day timer 8 M...

Страница 23: ...Integrated Control System 500 21...

Страница 24: ...Integrated Control System 500 22...

Страница 25: ...Integrated Control System 500 23...

Страница 26: ...e sure that the 3 conductor cable that connects from controller to PVR H does not have a short Disconnect power from the ICS 500 and PVR H Then disconnect 3 conductor cable from the PVR H and ICS500 m...

Страница 27: ...Backup System is not working at all 24 Make sure sensor is OK by disconnecting it from the backup board and checking it with a meter Put meter on Ohm s to see if it is broken or shorted Refer to the R...

Страница 28: ...2 1 78 454 2 7 16 3 28 915 36 3 2 4 76 268 3 6 15 8 28 482 36 9 2 7 74 149 4 5 15 3 28 057 37 4 3 0 72 095 5 4 14 8 27 777 37 8 3 2 70 105 6 3 14 3 27 363 38 3 3 5 68 557 7 0 13 9 26 957 38 8 3 8 66 6...

Страница 29: ...7 87 4 30 8 14 128 63 1 17 3 7 689 88 0 31 1 13 999 63 5 17 5 7 592 88 5 31 4 13 808 64 0 17 8 7 496 89 1 31 7 13 682 64 4 18 0 7 433 89 4 31 9 13 496 64 9 18 3 7 340 90 0 32 2 13 373 65 3 18 5 7 248...

Страница 30: ...40 9 4 284 113 9 45 5 5 076 106 2 41 2 4 217 114 6 45 9 4 995 106 9 41 6 4 168 115 2 46 2 4 936 107 4 41 9 4 120 115 7 46 5 4 877 108 0 42 2 4 057 116 4 46 9 4 820 108 5 42 5 3 995 117 1 47 3 4 763 10...

Страница 31: ...Integrated Control System 500 29...

Страница 32: ...Integrated Control System 500 30...

Страница 33: ...120V 6407 1211 PCB130 S05 CON 8 0 w QA 240V 6407 1214 PCB130 S05 CON 8 V w QA 6407 1216 PCB130 S05 TUN 8 0 w QA 6407 1218 PCB130 S05 OSC 8 V w QA 6407 1219 PCB130 S05 CON 8 V w QA 240V 6407 1220 PCB1...

Страница 34: ...ontrol System 500 32 Chart E Part No Description 6404 1174 PCB111 after QA 6404 1185 PCB115 after QA Chart F Part No Description 3008 2257 XFMR120V 24V40VA50 60PN_W 3008 2258 XFMR240V 24V40VA50 60PN_W...

Отзывы: