Level control with one fill factor 

Deplete 

Connect the level control completely and bring the sensor in position. Fill the receptacle in 
such a way that the sensor is a little immersed (maximum fill factor). 
Adjust front switch to: one level, filling, high sensitivity. Rotate potentiometer clockwise to the 
stop. Relay (R) must not be active. Now turn the potentiometer slowly counter clockwise to 
the left. If the left stop of the potentiometer is reached, turn it again clockwise until the right 
stop is reached. Adjust front switch to “low sensitivity” and turn the potentiometer again 
counter clockwise to the left. If the relay now switches automatically, the impedance of the 
liquid has fallen below. Now you have to turn back the potentiometer half turn. If you reach 
the right stop position before, switch back to „high sensitivity“ and execute the half turn to the 
right there. 
 
Set front switch to “emptying”. Now the relay should become active. The level control is now 
ready. 
 

Level control with two fill factors 

Fill 

Connect the level control completely and bring the sensors in position. Fill the receptacle in 
such a way that the sensor S2 is a little immersed (maximum fill factor). 
Adjust front switch to: two level, filling, high sensitivity. Rotate potentiometer clockwise to the 
stop. Relay (R) must not be active. Now turn the potentiometer slowly counter clockwise to 
the left. If the left stop of the potentiometer is reached, turn it again clockwise until the right 
stop is reached. Adjust front switch to “low sensitivity” and turn the potentiometer again 
counter clockwise to the left. If the relay now switches automatically, the impedance of the 
liquid has fallen below. Now you have to turn back the potentiometer half turn. If you reach 
the right stop position before, switch back to „high sensitivity“ and execute the half turn to the 
right there. The level control is now ready. 
 

Level control with two fill factors 

Deplete 

Connect the level control completely and bring the sensors in position. Fill the receptacle in 
such a way that the sensor S2 is a little immersed (maximum fill factor). 
Adjust front switch to: two level, filling, high sensitivity. Rotate potentiometer clockwise to the 
stop. Relay (R) must not be active. Now turn the potentiometer slowly counter clockwise to 
the left. If the left stop of the potentiometer is reached, turn it again clockwise until the right 
stop is reached. Adjust front switch to “low sensitivity” and turn the potentiometer again 
counter clockwise to the left. If the relay now switches automatically, the impedance of the 
liquid has fallen below. Now you have to turn back the potentiometer half turn. If you reach 
the right stop position before, switch back to „high sensitivity“ and execute the half turn to the 
right there. 
 
Set front switch to “emptying”. Now the relay should become active. The level control is now 
ready. 

Содержание TCL

Страница 1: ...to measure must have its conductivity within the available measuring range Make sure that the sensor cabling is placed within a shielded cable away from AC cabling or engine cabling Conductive liquids...

Страница 2: ...affin whiskey Measuring conductive liquids Measuring conductive liquids is not as easy as measuring the resistance of ohmic resistors The liquids are not completely ohmic and you have to avoid a mater...

Страница 3: ...S1 S2 are not covered It switches off as soon as both sensors get in contact with the medium Deplete Function The relay R becomes active as soon as both sensors S1 S2 are covered It switches off as s...

Страница 4: ...s you have to ground connection C of the TCL near the liquid receptacle The respective rules have to be considered Wire Use a shielded cable for the cabling The shield itself has to be connected with...

Страница 5: ...controls Other adjustments are conceivable and can be carried out by skilled engineers If the level control has a time delay f i TCL3 you have to set it to a minimum during calibration Adjust it to th...

Страница 6: ...ckwise to the stop Relay R must not be active Now turn the potentiometer slowly counter clockwise to the left If the left stop of the potentiometer is reached turn it again clockwise until the right s...

Страница 7: ...h two fill factors 6 CONTENT 7 Copyright 2003 HIQUEL GmbH Bairisch K lldorf 266 A 8344 Bad Gleichenberg This manual is subject to copyright law All rights are reserved Great care has been taken in the...

Отзывы: