background image

 

 

 

   

Cautions in Operation 
*Before operating this transformer, read this manual for proper and safety use. 
*Use this transformer under the proper voltage. 
*Use in a well-ventilated place. 
*This transformer must be place in the clean and dry room and kept away from oil, corrosive gas, 

Interference noise, high voltage unit and the like. 

*Note the lot number and inspection sheet number. 
*Before operation, this transformer must be grounded. 
*Spare transformer in order to avoid the unnecessary rotation of driver 
*Set the proper overtime for tightening screw to work the reset function of the transformer in 

order to avoid the unnecessary rotation of driver. 

*If the overtime continues, resolve the cause and re-start the unit. 
*When you install the unit, allow some slack for wiring of control terminal or power code. 

However, too much slack or unreasonable wiring: ex. binding the power code and signal wires 
together will be cause of trouble. 

*This unit should be installed in the system where it can be easily seen and removed. 
*Whenever the change of I/O setting or replacement of unit, the power code must be unplugged 
  And confirmed the safety of all systems. All setting must be same before and after replacement. 
*Use this transformer only for control the designated automatic driver manufactured by HIOS. 
 
  Note: Never use this for the manual drivers. It may cause trouble. 

 

 
 
 
 
 
 
 

 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 

     Model

 Driver moldes can

be connected

CLF-3000(HH/HN)
CLF-4000 (HH, XH/HN, XN)
CLF-6000 (HH, XH/HN, XN)
CLF-6500 (HH, XH/HN, XN)
CLF-7000 (HH, XH/HN, XN)

αF-4500 (HH, XH/HN, XN)
αF-5000 (HH, XH/HN, XN)
αF-6500 (HH, XH/HN, XN)

For CLT-AY-61 Applicable automatic driver

   1 driver only

     Model

 Driver moldes can

be connected

CL-816(XH/XN)
CL-825A(XH/XN)
CL-815A(XH/XN)

For CLT-AY-81 Applicable automatic driver

   1 driver only

Содержание CLT-AY-61

Страница 1: ...atic Controlled Systems For Electric Screwdrivers Operation Manual CLT AY 61 CLT AY 81 March 2017 HIOS Inc 1 16 5 Akiyama Matsudo City Chiba Pref Japan Phone 81 47 392 2001 FAX 81 47 392 7773 Operation Manual No ET A035 17A ...

Страница 2: ...ble of Contents Cautions in Operation 2 Selection of Controllers 2 Name of Each Part 3 4 Setting of switches on the PCB 5 Input and Output circuit 6 Timing Chart for Pulse input starting system 7 Timing Chart for Reading starting system 8 Timing Chart of Option REV Starting System 9 Timing Chart of Option 2WV Starting System 9 Notice of using Transformer for Multiple Axes 10 Procedure of Setting a...

Страница 3: ...ontrol terminal or power code However too much slack or unreasonable wiring ex binding the power code and signal wires together will be cause of trouble This unit should be installed in the system where it can be easily seen and removed Whenever the change of I O setting or replacement of unit the power code must be unplugged And confirmed the safety of all systems All setting must be same before ...

Страница 4: ...rns on while any trouble is occurred on tightening or overtime condition Note In case that output circuit is short or load is over CL PULSE and RESET LEDs turn on simultaneously and output to the motor of driver will be stopped In such case check the driver OPTIONS Followings are optional specifications 2WV This lamp turns on while the driver works at Low Level of rotation described at the optiona...

Страница 5: ...at the both end of the terminal When you do it unscrew each of screw little by little The table below is the status of switches of the PCB set at HIOS factory If you change the setting refer to the section of Input Output setting Fuse Holder 1 each of Fuse and Spare Fuse are installed If the Fuse is cut then the lamp of AC Switch and LED lamps do not lit replace with Spare Fuse ...

Страница 6: ...ward Rear Panel side R Reading Starting SW102 You can use both types H type or N type of automatic driver manufactured by HIOS The delivery time setting is for H type SW102 is placed toward Rear Panel side XH H type HIOS specification toward Front Panel side XN N type Nittoh specification SW103 You ca select the way of input Open collector Input Voltage Input The delivery time setting is the open ...

Страница 7: ...6 Input and Output circuit ...

Страница 8: ...hart indicates that driver was stopped by RESET signal T6 This signal is output to the Transformer from driver when from driver when the torque of driver reaches the fixed value Monitoring of input signal is possible with the FUNCTION LED T7 The timing is changed as the dotted lines by the fixed value of torque up Counter T8 This signal is output when the torque of driver reaches the fixed value a...

Страница 9: ...ION LED T4 The rotation of driver is indicated Monitoring of signal is possible with the FUNCTION LED T5 This chart indicates that driver was stopped by RESET signal T6 This signal is output to the Transformer from driver when from driver when the torque of driver reaches the fixed value Monitoring of input signal is possible with the FUNCTION LED T7 The timing is changed as the dotted lines by th...

Страница 10: ...9 Timing Chart of Option REV Starting System Timing Chart of Option 2WV Starting System ...

Страница 11: ... are connected the capacity of current should not exceed the range of possibility to be driver by sequencer or controller Procedure of Setting and Installation When the installation or setting this Transformer read this manual well be make sure the safety operation CAUSION Whenever installing or setting the Transformer must be unplugged 1 Confirm the matching or driver 2 Select all built in switch...

Страница 12: ...11 CLT AY 61 CLT AY 81 Power supply for Automatic screwdriver CLT AY 61 2WV option 2WV REV or 2WV REV Option CLT AY 81 Specifications ...

Страница 13: ...ive 3 Screw driver Hios product HH XH or Nittoh Seikou product HH XN are applicable Each selection or adjustment is changeable even after purchase See the instructions 5 Monitoring Input Output function is possible with the function LED on the front panel Provided LED are STRAT PLAYING CL PULSE FINGISH RESET and so on 6 The inlet with fuse holder is adopted The counter switch is designed to select...

Страница 14: ...elow is the table of China RoHS2 In addition if the following mark cannot be found at the rear side of the product and or Product box cut off a mark and stick a mark to the product and or product box Note minimum size of China RoHS mark is 5mm at outer diameter ...

Отзывы: