![HindlePower ATevo Series Скачать руководство пользователя страница 121](http://html.mh-extra.com/html/hindlepower/atevo-series/atevo-series_operations_2136863121.webp)
13.
13. Remote Sense
Remote Sense
ATevo regulates dc output voltage as measured at the charger’s output connection (CB2+/-).
The Remote Voltage Sense feature permits ATevo to monitor and regulate the dc output voltage
at the battery. This feature is useful when long battery cables, causing resistive voltage-drop,
connect ATevo to the battery. All ATevo chargers can be wired to utilize this feature.
SECTION
SECTION TOPICS
TOPICS
Configuring Remote Sense Jumpers
Last modified: 2 March 2021
13.1.
13.1. Remote Sense Connection
Remote Sense Connection
Remote sensing:
• Compensates for voltage drop in dc wiring between ATevo and the battery.
• Directly monitors battery or dc bus voltage. The front panel meter displays actual voltage
at the battery or dc bus.
SCHEMATIC
SCHEMATIC
To wire ATevo for remote sensing, install twisted-pair cabling from the remote sense terminals