X-SB 01
3 Product Description
HI 801 007 E Rev. 4.00
Page 17 of 38
3.4.8 Slot
Indicators
The slot indicator LEDs are located after the
Slot
label.
LED
Color
Status
Description
Green
On
Module inserted in slot X, logical connection established.
Yellow Blinking1 Module inserted in slot X, logical connection not
established.
3...18
Off
Off
Slot X not used
Table 9:
Slot Indicators
3.4.9 Diagnostic
Indicators
Diagnostic indicators reserved for future applications!
3.4.10 Ethernet
Indicators
The communication LEDs are labeled
Ethernet
.
LED
Color
Status
Description
Blinking-x
Communication detected on interface.
Blinking1
IP address conflict detected.
LEDs adjacent to one another,
PADT and H/F/Col blinking
PADT
Green
Off
PADT not connected.
On
Speed = 100 Mbit/s
Blinking-x not
defined!
Blinking1
IP address conflict detected.
LEDs adjacent to one another,
PADT
and
H/F/Col
blinking
H/F/Col
(PADT)
Yellow
Off
Speed = 10 Mbit/s or no connection.
On
System bus module connected, physical connection
established.
Up
Green
Off
No system bus module connected.
On
System bus module connected, physical connection
established.
Down
Green
Off
No system bus module connected.
On
Diagnostic device connected, physical connection
established
Diag
Green
Off
No diagnostic device connected.
On
Full duplex operation on the
F
line
Blinking-x
Collision detected on the
Col
line
H/F/Col
(Up,
Down,
Diag)
Yellow
Off
Half duplex operation on
H
line
Table 10: Communication Indicators