X-MIO 7/6 01
4 Start-up
HI 801 305 E Rev. 5.00
Page 51 of 72
4.5.6
Tab: I/O Submodule DI 02: Channels
The
I/O Submodule DI 02: Channels
tab contains the following system parameters for each
input. Global variables can be assigned to the statuses and parameters with
->
and used in the
user program. The value without
->
must be directly entered.
Name
Data type R/W
Description
Channel no.
---
R
Channel number, defined by default
T on [µs]
UDINT
W
Time on delay
Default setting: 0
It is only displayed in the redundancy group tab!
T off [µs]
UDINT
W
Time off delay
Default setting: 0
It is only displayed in the redundancy group tab!
Sup. used
BOOL
W
Activated: DI supply errors affect the
-> Channel OK
parameter.
Deactivated: Error in the DI supply does not affect the
-> Channel OK
parameter.
Default setting: Activated
It is only displayed in the redundancy group tab!
-> Channel Value
[BOOL]
BOOL
R
Binary value in accordance with the switching level LOW
(dig) and HIGH (dig).
TRUE: Channel energized
FALSE: Channel de-energized
-> Channel OK
BOOL
R
TRUE: Faultless channel
The channel value is valid.
FALSE: Faulty channel
The channel value is set to FALSE.
Table 31: Tab I/O Submodule DI 02: Channels in the Hardware Editor