X-DI 16 01
4 Start-up
HI 801 057 E Rev. 4.00
Page 33 of 54
4.3
Configuring the Module in SILworX
The module is configured in the Hardware Editor of the SILworX programming tool.
Observe the following points when configuring the module:
To diagnose the module and channels, both the statuses and the measured value can
be evaluated within the user program. For more information on the statuses and
parameters, refer to the tables starting with Chapter 4.3.
The channel supply is monitored. If the
Supply used
parameter is activated, a supply
error results in a channel fault (
Channel OK
= FALSE). If the channel supply is not used,
the
Supply used
parameter must be deactivated. This ensures that a supply error does
not lead to a channel fault (-> Channel OK = TRUE). To diagnose the supply in use,
evaluate the
Supply X OK
status in the user program. Refer to Table 19 for more details
about the
Supply X OK
status.
If a redundancy group is created, its configuration is defined in the tabs. The tabs
specific to the redundancy group differ from those of the individual modules, see the
following tables.
To evaluate the statuses from within the user program, assign the module statuses global
variables. Perform this step in the module's detail view of the Hardware Editor.
The following tables present the statuses and parameters for the module in the same order
given in the SILworX Hardware Editor.
TIP
To convert hexadecimal values to bit strings a scientific calculator such as the Windows
®
calculator with the corresponding view can be used.