X-DI 16 01
4 Start-up
HI 801 057 E Rev. 4.00
Page 35 of 54
4.3.2
Tab: I/O Submodule DI16_01
The
I/O Submodule DI16_01
tab contains the following statuses and parameters:
Name
R/W
Description
This parameter cannot be changed.
Name W
Module
name
External Power Supply
W
on: use external power supply
off: do not use external power supply
Default setting: on
Name
Data type R/W
Description
The following statuses and parameters can be assigned global variables and used in the user program.
Diagnostic Request
DINT
W
To request a diagnostic value, the appropriate ID must be
sent to the module using the parameter
Diagnostic
Request
(see Chapter 4.3.5 for coding details).
Diagnostic Response
DINT
R
As soon as
Diagnostic Response
returns the ID of
Diagnostic Request
(see 4.3.5 for coding details),
Diagnostic Status
contains the diagnostic value
requested.
Diagnostic Status
DWORD
R
Requested diagnostic value in accordance with
Diagnostic Response.
The IDs of
Diagnostic Request
and
Diagnostic Response
can be evaluated in the user program.
Diagnostic Status
only contains the requested diagnostic value when both
Diagnostic Request and Diagnostic Response have the
same ID.
Background Test Error BOOL
R
TRUE: Background test is faulty
FALSE: Background test is free of faults
Restart on Error
BOOL
W
Using the parameter
Restart on Error
, each I/O module
that has switched off permanently due to faults can be
forced to re-adopt the RUN state. To do this, set the
Restart on Error
parameter FALSE to TRUE.
The I/O module performs a complete self-test and only
enters the RUN state if no faults are detected.
Default setting: FALSE
Supply 1 OK
BOOL
R
The supplies are monitored for low voltage
TRUE: The supply is faultless.
FALSE: The supply is faulty.
Supply 2 OK
BOOL
R
Such as
Supply 1 OK
Supply 3 OK
BOOL
R
Such as
Supply 1 OK
Supply 4 OK
BOOL
R
Such as
Supply 1 OK
Supply 5 OK
BOOL
R
Such as
Supply 1 OK
Supply 6 OK
BOOL
R
Such as
Supply 1 OK
Supply 7 OK
BOOL
R
Such as
Supply 1 OK
Supply 8 OK
BOOL
R
Such as
Supply 1 OK
Submodule OK
BOOL
R
TRUE: No submodule fault
No channel faults
FALSE: Submodule fault
Channel fault (external faults included)
Submodule Status
BOOL
R
Bit-coded submodule status (see 4.3.4 for coding details)
Table 19: Tab: I/O Submodule DI16_01 in the Hardware Editor