X-DI 16 01
4 Start-up
HI 801 057 E Rev. 4.00
Page 37 of 54
Name
Data
Type
R/W
Description
Redundancy value
BYTE
W
Setting for determining the redundancy value.
And
Or
Default setting: Or
It is only displayed in the redundancy group tab!
Table 20: Tab: I/O Submodule D64_01:Channels in the Hardware Editor
4.3.4 Submodule
Status [DWORD]
Coding of the variable
Submodule Status
.
Coding
Description
0x00000001
Hardware unit fault (submodule).
0x00000002
Reset of an E/A bus
0x00000004
Faults detected while configuring the hardware
0x00000008
Fault detected while verifying the coefficients
0x00000080
Reset of the chip select monitoring
0x04000000
Module fault reference voltage B
0x08000000
Fault auxiliary voltage
0x10000000
Fault reference voltage A
0x20000000
Fault reference voltage B
0x40000000
Fault chip select monitoring A
0x80000000
Fault chip select monitoring B
Table 21: Submodule Status [DWORD]