3 Product Description
X-AO 16 01
Page 26 of 52
HI 801 111 E Rev. 4.00
3.7
System Cable X-CA 011
The X-CA 011 system cable is used to wire the X-CB 014 03/04 connector board with the
field zone via field termination assemblies.
General
Cable
LIYCY-TP 18 x 2 x 0.25 mm²
Wire
Finely stranded
Average outer diameter (d)
approx. 12.7 mm
Minimum bending radius
Fixed laying
Flexible application
5 x d
10 x d
Combustion behavior
Flame resistant and self-extinguishing in
accordance with IEC 60332-1-2, -2-2
Length 8…30
m
Color coding
Based on DIN 47100, see Table 15.
Table 17: Cable Data
Identical Cable Plugs
Figure 8: System Cable X-CA 011 01 n
The system cable is available in the following standard variants:
System cable
Description
Length
X-CA 011 01 8
8 m
X-CA 011 01 15
15 m
X-CA 011 01 30
Coded cable plugs on both sides
30 m
Table 18: Available System Cables