4 Start-Up
F2 DO 16 01
Page 26 of 40
HI 800 159 E Rev. 1.01
4.3.2.1
Module
Tab
The
Module
tab contains the following system parameters.
System parameter
Data
type
R/W Description
DO.Error Code
WORD
R
Error codes for all digital outputs
Coding
Description
0x0001
Fault within the digital outputs
0x0002
MOT test of safety shutdown returns a fault
0x0004
MOT test of auxiliary voltage returns a fault
0x0008
FTT test of test pattern faulty
0x0010
MOT test of output switch test pattern faulty
0x0020
MOT test of output switch test pattern
(shutdown test of the outputs) faulty
0x0040
MOT test active shutdown via WD faulty
0x0100
Outputs 1...4 and 9...12 de-energized due
to total current overrun
0x0200
Outputs 5...8 and 13...16 de-energized due
to total current overrun
0x0400
FTT test: 1st temperature threshold
exceeded
0x0800
FTT test: 2nd temperature threshold
exceeded
0x1000
FTT test: Monitoring of auxiliary voltage 1:
Low voltage
0x2000
FTT test: Monitoring of auxiliary voltage 2:
Low voltage
Module Error Code
WORD
R
Module error code
Coding
Description
0x0000
I/O processing, if required with errors, see
other error codes
0x0001
No I/O processing (device not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: incorrect configuration
0x0020
No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not
plugged in
Module SRS
UDINT
R
Slot number (System Rack Slot)
Module Type
UINT
R
Type of module, target value: 0x005A [90
dec
]
Table 16: SILworX - System Parameters for Digital Outputs,
Module
Tab