F2 DO 16 01
4 Start-Up
HI 800 159 E Rev. 1.01
Page 23 of 40
4.1.2
Connecting the Operating Voltage
Each group includes 8 channels. The two groups are supplied individually with separate
operating voltages, however, both clamp terminal blocks must be connected.
A group's total current input must not exceed 9 A. If a group exceeds the total current input,
it is switched off and then switched on again cyclically.
Group
Clamp terminal block
output channels
D1 (left)
L-, L-, L+1, L+1
1...4 and 9...12
D2 (right)
L-, L-, L+2, L+2
5...8 and 13...16
Table 15: Connecting the Operating Voltage