3 Product Description
F2 DO 16 01
Page 12 of 40
HI 800 159 E Rev. 1.01
WARNING
For connecting a load to a 1-pole switching output, use the corresponding L- ground
of the respective channel group (2-pole connection) to ensure that the internal
protective circuit can function.
Inductive loads may be connected without a free-wheeling diode on the actuator. However,
HIMA strongly recommends connecting a protective diode directly to the actuator.
If communication is lost, the output is set to the initial value configured. This effect must be
taken into account for the behavior of the connected output.
If an overload occurs, one or all outputs are switched off. If the overload is removed, the
outputs are switched on again automatically, see Table 12.
3.1.1.1
Reaction in the Event of a Fault
If the device detects a faulty signal on a digital output, the affected module output is set to
the safe (de-energized) state using the safety switches.
If a fault in the device occurs, all digital outputs are switched off.
In both cases, the devices activates the
FAULT
LED.
The error code allows the user to configure additional fault reactions in the user program.